ABB REU 610 Technical Reference Manual page 126

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
126
Voltage Relay
Technical Reference Manual - ANSI Version
Table 5.2.3.-10 Environmental tests and conditions (Continued)
Dry heat test
Dry cold test
Damp heat test, cyclic
Table 5.2.3.-11 Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below:
1 MHz burst disturbance test, class III
-Common mode
-Differential mode
Electrostatic discharge test, class IV
-For contact discharge
-For air discharge
Radio frequency interference tests:
-Conducted, common mode
-Radiated, amplitude-modulated
-Radiated, pulse-modulated
Fast transient disturbance tests
-Power outputs, energizing inputs, power
supply
-I/O ports
Surge immunity test
-Power outputs, energizing inputs, power
supply
-I/O ports
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
Voltage dips and short interruptions
Electromagnetic emission tests
-Conducted, RF-emission (Mains
terminal)
-Radiated RF-emission
CE approval
According to IEC 60068-2-2
According to IEC 60068-2-1
According to IEC 60068-2-30
According to IEC 60255-22-1
2.5 kV
1.0 kV
According to IEC 61000-4-2, IEC 60255-
22-2 and ANSI C37.90.3-2001
8 kV
15 kV
According to IEC 61000-4-6 and
IEC 60255-22-6 (2000)
10 V (rms), f = 150 kHz...80 MHz
According to IEC 61000-4-3 and
IEC 60255-22-3 (2000)
10 V/m (rms), f = 80...1000 MHz
According to the ENV 50204 and
IEC 60255-22-3 (2000)
10 V/m, f = 900 MHz
According to IEC 60255-22-4 and
IEC 61000-4-4
4 kV
2 kV
According to IEC 61000-4-5
4 kV, line-to-earth
2 kV, line-to-line
2 kV, line-to-earth
1 kV, line-to-line
300 A/m continuous
According to IEC 61000-4-11
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
According to the EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25
Complies with the EMC directive 89/336/
EEC and the LV directive 73/23/EEC
1MRS755972