ABB REU 610 Technical Reference Manual page 96

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
Table 5.1.17.-7 Control parameters
Description
Reading of the event buffer
Re-reading of the event buffer
Reading of relay state data
Resetting of relay state data
Time reading and setting
Date and time reading and setting
Type designation of the relay
Unlatching output contacts
Clearing targets and memorized values and
unlatching contacts (master reset)
Resetting of trip lockout
Rated frequency
Time setting range for demand values in
minutes
Non-volatile memory settings
Time setting for disabling new trip targets on
the LCD
96
Voltage Relay
Technical Reference Manual - ANSI Version
Table footnotes from previous page
a)
0 = rising edge; 1 = falling edge.
Table 5.1.17.-6 Disturbance recorder external triggering and storing
Event
Weighting
factor
DI1
1
DI2
2
DI3
4
DI4
8
DI5
16
Σ
a)
0 = rising edge; 1 = falling edge.
Control parameters
Parameter
L
B
C
C
T
D
F
V101
V102
V103
V104
V105
V106
V108
Default value
Default value
of triggering
of triggering
mask, V241
edge, V242
0
0
0
0
0
0
R, W, P
Value
R
Time, channel number and event code
R
Time, channel number and event code
R
0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2
W
0 = Reset E50 and E51
1 = Reset only E50
2 = Reset only E51
4 = Reset all events including E51 except
for E50
R, W
SS.sss
R, W
YY-MM-DD HH.MM;SS.sss
R
REU 610
W
1 = Unlatch
W
1 = Clear and unlatch
W
1 = Reset
R, W (P)
50 or 60 Hz
R, W
0...999 min
R, W
0...31
R, W (P)
0...999 min
1MRS755972
Default value
of storing
a)
mask, V243
0
0
0
0
0
0
0
0
0
0
0
0

Advertisement

Table of Contents
loading

Table of Contents