Powerware Ferrups FE/QFE UPS User Manual page 24

500 va–18 kva,50 and 60 hz
Table of Contents

Advertisement

UPS Startup
3. The AC LINE indicator illuminates (see Figure 2).
NOTE The AC LINE indicator does not illuminate for FE models with serial numbers
25000 and greater until the UPS ON/OFF switch is turned to the ON position.
4. If you have an external battery cabinet with a DC switch, turn
5. Turn the UPS ON/OFF switch to the ON position. After a short
NOTE The UPS and external battery cabinets are shipped with the batteries charged.
However, batteries may lose some of the charge during shipping and storage. You can
use the UPS immediately after unpacking, but it may not provide the full-rated backup
time during a power failure. Upon initial startup, the UPS may need to operate for
24 hours before the battery is fully charged and full battery-backup time is available. If
the CHARGING indicator is illuminated, operate the UPS for 24 hours to fully charge
the battery.
6.
NOTE For QFE models, use the supplied UPS cord to connect your equipment to the
UPS output receptacles.
7. Turn on the equipment that is connected to the UPS.
18
AC LINE
READY
Figure 2. Front Panel Indicators
the switch to the ON position.
startup test, the READY indicator flashes for a few seconds and
then remains illuminated. The UPS is ready to supply output
power.
For Plug-Receptacle UPSs:
into the UPS output receptacles.
Turn the bypass switch to the UPS position.
For Hardwired UPSs:
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide
ALARM
CHARGING
BATTERY
POWER
Plug the equipment to be protected
Rev A www.powerware.com