Powerware Ferrups FE/QFE UPS User Manual page 67

500 va–18 kva,50 and 60 hz
Table of Contents

Advertisement

Letter
Audio
Alarm
Code
Message
J
– – –
User Test
Alarm
K
– –
Hi
Transfmr
Temp
L
Check
Charger
M
– –
Check
Battery
N
Check
Inverter
O
– – –
Memory
Check
P
– –
Emergency
PwrOff
Q
– – –
Hi PFM
Res
Temp
R
Probe
Missing
S
High AC
Input
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide
What It Means
The user is testing the alarm feature.
The transformer temperature is too high. If
the temperature reaches a preset point, the
UPS shuts down.
The UPS has detected a charger problem.
The batteries have failed the automatic
system test.
The inverter has failed the automatic
system test.
Possible microprocessor problem.
The Remote Shutdown feature has been
activated at the RS-232 port (see "Remote
Shutdown" on page 47.)
The Power Factor Module's temperature is
too high. If the temperature reaches a
preset point, the UPS shuts down.
A temperature probe is missing or
damaged.
The input voltage is higher than the alarm
setting.
Rev A www.powerware.com
Troubleshooting
What To Do
To start the user test alarm from the
control panel, press [CTRL]-[8] [ENTER]
[ENTER]. Repeat the procedure to turn the
alarm off.
The UPS may have shut down; if so,
contact your service representative. If the
UPS has not shut down, shut down your
equipment or bypass the UPS; then, turn
the UPS off and contact your service
representative.
Contact your service representative.
Contact your service representative.
Contact your service representative.
Shut down your equipment or bypass the
UPS; turn off the UPS. Contact your service
representative.
To restart the UPS, disconnect the signal to
Pin 21 on the RS-232 port. If you have a
control panel, put the UPS in Auto mode. If
not, turn the On/Off switch off and then on
again.
If the UPS has shut down, contact your
service representative. If not, shut down
your equipment or bypass the UPS; then,
turn the UPS off and contact your service
representative.
The UPS may shut down. Contact your
service representative.
Contact your service representative.