Powerware Ferrups FE/QFE UPS User Manual page 40

500 va–18 kva,50 and 60 hz
Table of Contents

Advertisement

Operation
Parameter
Sample Display
Number
14
14 XfmrTemp 28c
15
15 Unit ID
Network #1 UPS
16
16 FullLoad% 075
17
17 Watts 374
18
18 PF 0.73 Dist
19
19 VALimit 500
20
20 #PwrOut 1
21
21 #OvrLds 0
22
22 SysHrs 00000
23
23 InvMin 0000.0
34
Password
Parameter Name
(Short Form)
Change Not
xfmrtemp
Allowed
(xt)
None
unitident
(See "Entering
(id)
Passwords" on
page 28.)
Change Not
fullload
Allowed
(l)
Change Not
watts
Allowed
(w)
Change Not
powerfact
Allowed
(pf)
Change Not
valimit
Allowed
(val)
Change Not
powerout
Allowed
(po)
Change Not
overloads
Allowed
(ol)
Change Not
syshours
Allowed
(sh)
Change Not
invmin
Allowed
(im)
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide
Explanation
The temperature of the transformer. The UPS
sounds an alarm and shuts down if this value
is too high.
This parameter is only active on some
models; for other models, the display always
shows -63c.
UPS ID. An identification string that can be
configured for use with your network.
Percent of Full Load. The percentage of the
UPS's total capacity that is actually being
used by your equipment.
The total "real power" your equipment is
drawing from the UPS.
The power factor of your equipment; the
difference in the way it draws voltage and
current. Power factor is equal to Watts Out
(parameter 17) divided by VA Out
(parameter 5). This parameter also tells
whether the power factor is leading (Lead),
lagging (Lag), or distortion (Dist).
The maximum volt-amps the UPS can supply
to your equipment at the present power
factor. The UPS sounds an alarm when VA
Out (parameter 5) is higher than this value.
The number of times there has been a loss of
input power since you started the UPS.
The number of times the UPS has sensed an
overload; that is, the number of times VA Out
has been greater than VA Limit.
The total number of hours the UPS has been
operating, regardless of mode. This number
does not increase when the UPS ON/OFF
switch is in the OFF position.
The total number of minutes the inverter has
run since startup.
Rev A www.powerware.com