Command
Short
Form
date
da
delay
dl
display
d
extendedhistory
xh
format
f
help
? or he
history
h
identify
I
inverterlog
il
logs
l
off [time]
o [time]
off [time] autostart
o [time]
a
off cancel
o c
parameters
p
*If you change parameter 39 to "Yes," this command requires a User password.
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide
Password
Function
None*
Displays system time and date. To set the date, enter
None
Delays next command when you enter a number after
represents 2.5 milliseconds, so
delay. For a 1-second delay, enter
Depends
Displays the values of one or more parameters (see Table 4 on page 32).
on
Format: display [parameter # or name] [parameter # or name]
parameter
Example:
password
None
Displays the minimum and maximum values of parameters 1 (Vac In),
2 (Vac Out), 7 (Vdc) and 5 (VA Out); the command then clears the
minimum and maximum values (see Table 4 on page 32).
None
Displays an 80-character line containing information on the FERRUPS'
status. CheckUPS II and other UPS monitoring software use this data.
None
Shows a list of terminal/computer commands.
None
Displays the minimum and maximum values of parameter 1 (Vac In); the
command then clears the minimum and maximum values.
None
Shows Powerware's address and telephone number and the software
version.
None
Displays the Inverter Log. See "Alarm and Inverter Logs" on page 62.
None
Displays both the Alarm and Inverter Logs. See "Alarm and Inverter Logs"
on page 62.
None*
Shuts down the UPS a given number of seconds. The READY indicator
flashes until the UPS shuts down, and the UPS beeps five seconds before
shutdown. Example:
None*
Shuts down the UPS in a given number of seconds (see above), and
restarts the UPS shortly after power returns.
None*
Cancels timed shutdown.
Depends
Shows a list of system parameters. See "Parameters" on page 32. You
on
can also display a range of parameters by entering the starting and
parameter
ending parameter number or name after the command.
password
Example:
Rev A www.powerware.com
.
would cause a 2.5 millisecond
.
displays the values of parameters 1, 16 and 21
shuts down the UPS in 60 seconds.
displays parameters 1 through 10.
Communication
. Each unit
45