CHAPTER 7: COMMANDS AND TARGETS
DIRECT I/O FAILURE:
COMM Path Incomplete
Latched target message: No.
Description of problem: A direct device is configured but not connected.
How often the test is performed: Every second.
What to do: Check direct input and output configuration and wiring.
RxGOOSE FAIL:
Missing messages
Latched target message: No.
Description of problem: One or more RxGOOSE messages are not being received.
How often the test is performed: The self-test is activated when no message is received within the expected time
interval, which is the time-to-live time in the previous message. This time can be from milliseconds to minutes.
What to do: Check GOOSE setup.
AGGREGATOR ERROR:
Latched target message: No.
Description of problem: The second line of this self-test error indicates the problem with the PMU Aggregator.
How often the test is performed: Each time a PMU's related settings is changed.
What to do: Correct the problem indicated in the second line or contact the factory.
TEMP MONITOR:
OVER TEMPERATURE
Latched target message: Yes.
Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C).
How often the test is performed: Every hour.
What to do: Remove the C60 from service and install in a location that meets operating temperature standards.
UNEXPECTED RESTART:
Press "RESET" key
Latched target message: Yes.
Description of problem: Abnormal restart from modules being removed or inserted while the C60 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
How often the test is performed: Event driven.
What to do: Contact the factory.
FIRST ETHERNET FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
Latched target message: Yes.