CHAPTER 5: SETTINGS
The trip output element is primarily used to collect trip requests from protection elements and other inputs to generate
output operands to initiate trip operations. Three pole trips only initiate reclosure if programmed to do so, whereas single
pole trips always automatically initiate reclosure. The TRIP 3-POLE and TRIP 1-POLE output operands can also be used as
inputs to a FlexLogic OR gate to operate the faceplate Trip indicator LED.
5.8.5.1 Three pole operation
In applications where single-pole tripping is not required this element provides a convenient method of collecting inputs to
initiate tripping of circuit breakers, the reclose element and breaker failure elements.
5.8.5.2 Single pole operation
This element must be used in single pole operation applications.
This element is used to:
Determine if a single pole operation is to be performed
Collect inputs to initiate three pole tripping, the recloser and breaker failure elements
Collect inputs to initiate single pole tripping, the recloser and breaker failure elements
Assign a higher priority to pilot aided scheme outputs than to exclusively local inputs
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
TRIP RESET:
CBaux OR Custom
START TMR Z2PH Inp1:
Off
START TMR Z2PH Inp2:
Off
START TMR Z2GR Inp1:
Off
START TMR Z2GR Inp2:
Off
PH SELECTOR RESET
DELAY: 0.500 s
PH SELECTOR RESET:
Off
TRIP FORCE 3-POLE:
Off
TRIP PILOT PRIORITY:
0.000 s
REVERSE FAULT:
Off
TRIP DELAY ON EVOLV
FAULTS: 0.000 s
BKR ΦA OPEN:
Off
BKR ΦB OPEN:
Off
BKR ΦC OPEN:
Off
TRIP EVENTS:
Disabled
Range: Pole Curr OR Custom, CBaux OR Custom,
Custom
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.500 to 3.000 s in steps of 0.001 s
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: 0 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Enabled, Disabled
CONTROL ELEMENTS