GROUPED ELEMENTS
The C60 contains protection elements for neutral time overcurrent (ANSI device 51N) and neutral instantaneous
overcurrent (ANSI device 50N). A maximum of six neutral time overcurrent elements and eight neutral instantaneous
overcurrent elements are available, dependent on the CT/VT modules ordered with the relay. See the following table for
details.
5
CT/VT modules
Slot F
8F/8G
8H/8J
5.7.4.2 Neutral time overcurrent (ANSI 51N, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  NEUTRAL TOC1(4)
 NEUTRAL TOC1
5-202
 NEUTRAL IOC 1
 NEUTRAL IOC 2
 NEUTRAL IOC 3
 NEUTRAL IOC 4
 NEUTRAL IOC 5
 NEUTRAL IOC 6
 NEUTRAL IOC 7
 NEUTRAL IOC 8
Neutral current elements
Slot M
Time overcurrent
8F/8G
4
8H/8J
6
8F/8G
6
8H/8J
6
NEUTRAL TOC1
FUNCTION: Disabled
NEUTRAL TOC1 SIGNAL
SOURCE: SRC 1
NEUTRAL TOC1
INPUT: Phasor
NEUTRAL TOC1
PICKUP: 1.000 pu
NEUTRAL TOC1
CURVE: IEEE Mod Inv
NEUTRAL TOC1
TD MULTIPLIER: 1.00
NEUTRAL TOC1
RESET: Instantaneous
NEUTRAL TOC1 BLOCK:
Off
See page 5-203
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Instantaneous
overcurrent
4
6
6
8
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Phasor, RMS
Range: 0.020 to 30.000 pu in steps of 0.001
Range: see Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: FlexLogic operand
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL