CHAPTER 5: SETTINGS
The
setting is the DNP slave address. This number identifies the C60 on a DNP communications link. Assign a
DNP ADDRESS
unique address to each DNP slave.
The C60 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the C60 can connect. The settings follow.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP NETWORK CLIENT ADDRESSES
 DNP NETWORK
 CLIENT ADDRESSES
The
DNP TCP/UDP PORT NUMBER
takes effect when the C60 is restarted.
The
DNP UNSOL RESPONSE FUNCTION
mechanism. The
DNP UNSOL RESPONSE TIMEOUT
response. The
DNP UNSOL RESPONSE MAX RETRIES
unsolicited response without receiving confirmation from the master; a value of "255" allows infinite re-tries. The
UNSOL RESPONSE DEST ADDRESS
solicited responses are sent is determined by the C60 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the C60 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the
all DNP analog input points that are voltages are returned with values 1000 times smaller (for example, a value of 72000 V
on the C60 is returned as 72). These settings are useful when analog input values must be adjusted to fit within certain
ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value is 10 times larger).
The
settings determine when to trigger unsolicited responses containing analog input data. These
DNP DEFAULT DEADBAND
settings group the C60 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger
unsolicited responses from the C60 when any current values change by 15 A, the
is set to "15." Note that these settings are the deadband default values. DNP object 34 points can be used to change
deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and re-
applied to the C60, the default deadbands are in effect.
The
DNP TIME SYNC IIN PERIOD
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The
DNP MESSAGE FRAGMENT SIZE
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to
be necessary, which provides more robust data transfer over noisy communication channels.
Check the "DNP Points Lists" C60 web page to view the analog inputs and/or binary inputs points lists. This page
can be viewed with a web browser by entering the IP address of the C60 Ethernet port employed to access the C60
Main Menu, then by clicking the Device Information Menu item, then the DNP Points Lists item.
The
DNP OBJECT 1 DEFAULT VARIATION
number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation
0 is requested and/or in class 0, 1, 2, or 3 scans. See the DNP Implementation section in the UR Family Communications
Guide.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the C60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The C60 can be configured to
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 5:
0.0.0.0
setting is for normal DNP operation. To close the port, set the port number to 0. The change
is set to "Disabled" for RS485 applications since there is no collision avoidance
sets the time the C60 waits for a DNP master to confirm an unsolicited
setting determines the number of times the C60 retransmits an
is the DNP address to which all unsolicited responses are sent. The IP address to which
setting determines how often the Need Time Internal Indication (IIN) bit is set by the C60.
setting determines the size, in bytes, at which message fragmentation occurs. Large
to
DNP OBJECT 32 DEFAULT VARIATION
Range: standard IP address
Range: standard IP address
setting is set to "1000,"
DNP VOLTAGE SCALE FACTOR
DNP CURRENT DEFAULT DEADBAND
settings select the DNP default variation
PRODUCT SETUP
DNP
5
setting
5-41