GE C60 Instruction Manual page 206

Breaker protection system
Hide thumbs Also See for C60:
Table of Contents

Advertisement

PRODUCT SETUP
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
5.3.4.9 Protocol selection
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  PROTOCOL
 PROTOCOL
The
menu allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
PROTOCOL
— This setting selects the SCADA protocol on which the unit communicates, among DNP3.0, IEC 60870-
SCADA PROTOCOL
104, and IEC 60870-103, with DNP being the default. Options depend on order code. For any change to take effect, restart
the unit.
MMS CONNECTION TIMEOUT
no data traffic on the TCP connection for greater than the time specified by this setting, the connection is aborted. This
frees up the connection to be re-used by a client. For any change to take effect, restart the unit.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the
Table 5-9: Port and protocol combinations
5
PROTOCOL
DNP CHANNEL 1(2) PORT
setting
settings
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Channel 1: Eth TCP
Channel 2: none
Channel 1: none
Channel 2: Eth TCP
Channel 1: Eth UDP
Channel 2: none
Channel 1: Eth TCP
Channel 2: RS485
Channel 1: Eth TCP
Channel 2: RS232
Channel 1: Eth UDP
Channel 2: RS485
Channel 1: Eth UDP
Channel 2: RS232
Channel 1: RS485
Channel 2: Eth TCP
Channel 1: RS232
Channel 2: Eth TCP
Channel 1: RS485
Channel 2: RS232
Channel 1: RS232
Channel 2: RS485
Channel 1: RS485
Channel 2: none
IEC 104
IEC 103
5-38
SCADA PROTOCOL:
DNP 3.0
MMS CONNECTION
TIMEOUT: 120 s
— This setting specifies a time delay for the detection of network TCP connection lost. If there is
RS232
Modbus
Modbus
Modbus
Modbus
Modbus
DNP
Modbus
DNP
Modbus
DNP
DNP
DNP
Modbus
Modbus
Modbus
Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
Range: 10 to 7200 in steps of 10
and
PROTOCOL
RS485
Ethernet
Modbus
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
Modbus, IEC 61850
DNP
Modbus, IEC 61850
DNP
Modbus, IEC 61850
Modbus
IEC 104, Modbus, IEC 61850
IEC 103
Modbus, IEC 61850
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
settings.
DNP CHANNEL 1(2) PORT

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents