GE C60 Instruction Manual page 320

Breaker protection system
Hide thumbs Also See for C60:
Table of Contents

Advertisement

SYSTEM SETUP
Value (decimal)
 13
 14
5.5.7.8 Settings
The PMU settings are organized as follows.
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1(2)
 PHASOR MEASUREMENT
 UNIT 1
5.5.7.9 Basic configuration
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  BASIC CONFIGURATION  PMU 1(2)
 PMU 1 BASIC
 CONFIGURATION
5
5-152
Number of ASDUs
3
 4
 PMU 1 BASIC
 CONFIGURATION
 PMU 1
 CALIBRATION
 PMU 1
 TRIGGERING
 PMU 1
 RECORDING
PMU 1
FUNCTION: Disabled
PMU 1 IDCODE:
1
PMU 1 STN:
GE-UR-PMU
PMU 1 SIGNAL SOURCE:
SRC 1
PMU 1 CLASS:
M-CLASS
PMU 1 FORMAT:
Integer
PMU 1 STYLE:
Polar
PMU 1 RATE:
10/sec
PMU 1 f & df/dt
FILTER: None
 C37.118 PMU 1
 CONFIGURATION
PMU 1 PHS- 1:
Off
PMU 1 PHS-14:
Off
PMU 1 PHS- 1:
NM: GE-UR-PMU-PHS 1
PMU 1 PHS-14:
NM: GE-UR-PMU-PHS 14
See below
See page 5-155
See page 5-157
See page 5-163
Range:
Enabled, Disabled
Range:
1 to 65534 in steps of 1
Range:
32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
Range:
available signal sources
Range:
None, M-CLASS, P-CLASS
Range:
Integer, Floating-point
Range:
Polar, Rectangular
Range: 1, 2, 4, 5, 10, 12, 15,20, 25, 30,50, 60, 100, 120
/sec
Range: None, 10Hz/s <10Hz, 10Hz/s <20Hz, 20Hz/s
<10Hz, 20Hz/s <20Hz
See below
Range:
available synchrophasor values
Range:
available synchrophasor values
Range:
16-character ASCII string
Range:
16-character ASCII string
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents