CHAPTER 6: ACTUAL VALUES
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
— The number of IEC 61850 connections remaining.
MMS TCP
— The maximum number of PMU TCP connections matches the number of aggregators. The maximum number of
PMU TCP
aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with a
PMU. The remaining number of aggregators displays here.

6.3.21 Parallel Redundancy Protocol (PRP)

The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES  STATUS  PRP STATUS
 PRP STATUS
The C60 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port A
is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Received Port B
is a counter for total messages received with an error (bad port code, frame length too short).
Total Errors
is a counter for total messages received with an error on Port A (PRP frame, but port received through
Mismatches Port A
and LAN ID in the frame do not match).
is a counter for total messages received with an error on Port B (PRP frame, but port received through
Mismatches Port B
and LAN ID in the frame do not match).

6.3.22 TxGOOSE status

ACTUAL VALUES  STATUS  TxGOOSE STATUS
 TxGOOSE STATUS
The C60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Total Rx Port A:
0
Total Rx Port B:
0
Mismatches Port A:
0
Mismatches Port B:
0
Total Errors:
0
R-TxGOOSE 1
ARP:
Off
R-TxGOOSE 16
ARP:
Off
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: On, Off
Range: On, Off
STATUS
6