B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 51)
ADDR
REGISTER NAME
7083
Phase Distance Zone 1 Transformer Current Connection
7084
Phase Distance Zone 1 Rev Reach
7085
Phase Distance Zone 1 Rev Reach RCA
7086
Reserved (10 items)
7090
...Repeated for Phase Distance Zone 2
B
70B0
...Repeated for Phase Distance Zone 3
Ground Distance (Read/Write Grouped Setting) (5 modules)
7130
Ground Distance Zone 1 Function
7131
Ground Distance Zone 1 Current Supervision
7132
Ground Distance Zone 1 Reach
7133
Ground Distance Zone 1 Direction
7134
Ground Distance Zone 1 Comparator Limit
7135
Ground Distance Zone 1 Delay
7136
Ground Distance Zone 1 Block
7137
Ground Distance Zone 1 Target
7138
Ground Distance Zone 1 Events
7139
Ground Distance Zone 1 Shape
713A
Ground Distance Zone 1 Z0 Z1 Magnitude
713B
Ground Distance Zone 1 Z0 Z1 Angle
713C
Ground Distance Zone 1 RCA
713D
Ground Distance Zone 1 DIR RCA
713E
Ground Distance Zone 1 DIR Comp Limit
713F
Ground Distance Zone 1 Quad Right Blinder
7140
Ground Distance Zone 1 Quad Right Blinder RCA
7141
Ground Distance Zone 1 Quad Left Blinder
7142
Ground Distance Zone 1 Quad Left Blinder RCA
7143
Ground Distance Zone 1 Z0M Z1 Magnitude
7144
Ground Distance Zone 1 Z0M Z1 Angle
7145
Ground Distance Zone 1 Voltage Level
7146
Ground Distance Zone 1 Non-Homogeneous Angle
7147
Ground Distance Zone 1 POL Current
7148
Ground Distance Zone 1 Reverse Reach
7149
Ground Distance Zone 1 Reverse Reach RCA
714A
Reserved (7 items)
7151
...Repeated for Ground Distance Zone 2
7172
...Repeated for Ground Distance Zone 3
Line Pickup (Read/Write Grouped Setting)
71F0
Line Pickup Function
71F1
Line Pickup Signal Source
71F2
Line Pickup Phase IOC Pickup
71F3
Line Pickup UV Pickup
71F4
Line End Open Pickup Delay
71F5
Line End Open Reset Delay
71F6
Line Pickup OV Pickup Delay
71F7
Autoreclose Coordination Pickup Delay
71F8
Autoreclose Coordination Reset Delay
71F9
Autoreclose Coordination Bypass
71FA
Line Pickup Block
71FB
Line Pickup Target
71FC
Line Pickup Events
71FD
Terminal Open
71FE
Autoreclose Accelerate
Breaker Failure (Read/Write Grouped Setting) (2 modules)
7200
Breaker Failure 1 Function
B-32
RANGE
0 to 12
0.02 to 500
30 to 90
---
0 to 1
0.05 to 30
0.02 to 500
0 to 2
30 to 90
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 10
-90 to 90
30 to 90
30 to 90
30 to 90
0.02 to 500
60 to 90
0.02 to 500
60 to 90
0 to 7
-90 to 90
0 to 5
-40 to 40
0 to 1
0.02 to 500
30 to 90
0 to 65535
0 to 1
0 to 5
0 to 30
0 to 3
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 1
L60 Line Phase Comparison Relay
UNITS
STEP
FORMAT
---
1
F153
ohms
0.01
F001
degrees
1
F001
---
---
F001
---
1
F102
pu
0.001
F001
ohms
0.01
F001
---
1
F154
degrees
1
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F120
---
0.01
F001
degrees
1
F002
degrees
1
F001
degrees
1
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
0.01
F001
degrees
1
F002
pu
0.001
F001
degrees
0.1
F002
---
1
F521
ohms
0.01
F001
degrees
1
F001
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F102
APPENDIX B
DEFAULT
0 (None)
200
85
0
0 (Disabled)
200
200
0 (Forward)
90
0
0
0 (Self-reset)
0 (Disabled)
0 (Mho)
270
0
85
85
90
1000
85
1000
85
0
0
0
0
0 (Zero-seq)
200
85
0
0 (Disabled)
0 (SRC 1)
1000
700
150
90
40
45
5
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)