GE L60 Instruction Manual page 121

Line phase comparison relay, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
MESSAGE
MESSAGE
MESSAGE
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state 'heartbeat' time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
GSSE
MESSAGE
MESSAGE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
GSSE ID
string identifies the GSSE message to the receiving device. In L60 releases previous to 5.0x, this name string was repre-
sented by the
setting.
RELAY NAME
The fixed GOOSE settings are shown below:
PATH: SETTINGS
PRODUCT...
FIXED GOOSE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
COMMUNICATIONS
IEC 61850 PROTOCOL
GENERAL
GSSE
FIXED GOOSE
CONFIGURABLE
GOOSE
COMMUNICATIONS
IEC 61850...
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed L60 GOOSE, and configurable GOOSE.
COMMUNICATIONS
IEC 61850...
GSSE FUNCTION:
Enabled
GSSE ID:
GSSEOut
DESTINATION MAC:
000000000000
COMMUNICATIONS
IEC 61850...
GOOSE FUNCTION:
Disabled
GOOSE ID:
GOOSEOut
DESTINATION MAC:
000000000000
GOOSE VLAN PRIORITY:
4
GOOSE VLAN ID:
0
GOOSE ETYPE APPID:
0
L60 Line Phase Comparison Relay
5.2 PRODUCT SETUP
GSSE/GOOSE...
GSSE/GOOSE...
TRANSMISSION
Range: 1 to 60 s in steps of 1
GSSE/GOOSE...
TRANSMISSION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
GSSE/GOOSE...
TRANSMISSION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
Range: 0 to 7 in steps of 1
Range: 0 to 4095 in steps of 1
Range: 0 to 16383 in steps of 1
TRANSMISSION
5
GENERAL
GSEE
FIXED GOOSE
5-19

Advertisement

Table of Contents
loading

Table of Contents