APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 34 of 51)
ADDR
REGISTER NAME
Permissive overreach transfer trip (POTT) settings (read/write)
A070
POTT Scheme Function
A071
POTT Permissive Echo
A072
POTT Rx Pickup Delay
A073
POTT Transient Block Pickup Delay
A074
POTT Transient Block Reset Delay
A075
POTT Echo Duration
A076
POTT Line End Open Pickup Delay
A077
POTT Seal In Delay
A078
POTT Ground Direction OC Forward
A079
POTT Rx
A07A
POTT Echo Lockout
Selector switch actual values (read only)
A210
Selector switch 1 position
A211
Selector switch 2 position
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
A281
Selector 1 Range
A282
Selector 1 Timeout
A283
Selector 1 Step Up
A284
Selector 1 Step Mode
A285
Selector 1 Acknowledge
A286
Selector 1 Bit0
A287
Selector 1 Bit1
A288
Selector 1 Bit2
A289
Selector 1 Bit Mode
A28A
Selector 1 Bit Acknowledge
A28B
Selector 1 Power Up Mode
A28C
Selector 1 Target
A28D
Selector 1 Events
A28E
Reserved (10 items)
A298
...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300
DNP/IEC 60870-5-104 Binary Input Points (256 items)
A400
DNP/IEC 60870-5-104 Analog Input Points (256 items)
Flexcurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
A680
FlexCurve D (120 items)
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
A701
Non-Volatile Latch 1 Type
A702
Non-Volatile Latch 1 Set
A703
Non-Volatile Latch 1 Reset
A704
Non-Volatile Latch 1 Target
A705
Non-Volatile Latch 1 Events
A706
Reserved (4 items)
A70A
...Repeated for Non-Volatile Latch 2
A714
...Repeated for Non-Volatile Latch 3
A71E
...Repeated for Non-Volatile Latch 4
A728
...Repeated for Non-Volatile Latch 5
A732
...Repeated for Non-Volatile Latch 6
A73C
...Repeated for Non-Volatile Latch 7
A746
...Repeated for Non-Volatile Latch 8
A750
...Repeated for Non-Volatile Latch 9
GE Multilin
RANGE
0 to 1
0 to 1
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65535
0 to 65535
0 to 65.535
1 to 7
1 to 7
0 to 1
1 to 7
3 to 60
0 to 65535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 65535
0 to 2
0 to 2
0 to 1
---
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 2
0 to 1
---
L60 Line Phase Comparison Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F102
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F300
s
0.001
F001
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
0.1
F001
---
1
F300
---
1
F083
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F083
---
1
F300
---
1
F084
---
1
F109
---
1
F102
---
1
F001
---
1
F300
---
1
F300
ms
1
F011
ms
1
F011
---
1
F102
---
1
F519
0 (Reset Dominant)
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
DEFAULT
0 (Disabled)
0 (Disabled)
0
20
B
90
100
50
400
0
0
250
0
1
0 (Disabled)
7
50
0
0 (Time-out)
0
0
0
0
0 (Time-out)
0
0 (Restore)
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0
B-41