B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 51)
ADDR
REGISTER NAME
6126
CT Fail Voltage Source
6127
CT Fail Voltage Pickup
6128
CT Fail Pickup Delay
6129
CT Fail Target
612A
CT Fail Events
B
Continuous Monitor (Read/Write Setting)
6130
Continuous Monitor Function
6131
Continuous Monitor I OP
6132
Continuous Monitor I Supervision
6133
Continuous Monitor V OP
6134
Continuous Monitor V Supervision
6135
Continuous Monitor Target
6136
Continuous Monitor Events
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence Time Overcurrent 1 Function
6301
Negative Sequence Time Overcurrent 1 Signal Source
6302
Negative Sequence Time Overcurrent 1 Pickup
6303
Negative Sequence Time Overcurrent 1 Curve
6304
Negative Sequence Time Overcurrent 1 Multiplier
6305
Negative Sequence Time Overcurrent 1 Reset
6306
Negative Sequence Time Overcurrent 1 Block
6307
Negative Sequence Time Overcurrent 1 Target
6308
Negative Sequence Time Overcurrent 1 Events
6309
Reserved (7 items)
6310
...Repeated for Negative Sequence Time Overcurrent 2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
6400
Negative Sequence Instantaneous OC 1 Function
6401
Negative Sequence Instantaneous OC 1 Signal Source
6402
Negative Sequence Instantaneous Overcurrent 1 Pickup
6403
Negative Sequence Instantaneous Overcurrent 1 Delay
6404
Negative Sequence Instantaneous OC 1 Reset Delay
6405
Negative Sequence Instantaneous Overcurrent 1 Block
6406
Negative Sequence Instantaneous Overcurrent 1 Target
6407
Negative Sequence Instantaneous Overcurrent 1 Events
6408
Reserved (8 items)
6410
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting)
64A0
Negative Sequence Overvoltage Function
64A1
Negative Sequence Overvoltage Source
64A2
Negative Sequence Overvoltage Pickup
64A3
Negative Sequence Overvoltage Pickup Delay
64A4
Negative Sequence Overvoltage Reset Delay
64A5
Negative Sequence Overvoltage Block
64A6
Negative Sequence Overvoltage Target
64A7
Negative Sequence Overvoltage Events
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
B-28
RANGE
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 5
0 to 30
0 to 16
0 to 600
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
L60 Line Phase Comparison Relay
UNITS
STEP
FORMAT
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F103
---
0.01
F001
---
1
F104
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
APPENDIX B
DEFAULT
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (SRC 1)
1000
0 (IEEE Mod Inv)
100
0 (Instantaneous)
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
50
50
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75