5.2 PRODUCT SETUP
If the
PUSHBTN 1 MESSAGE
settings will be displayed as long as
by
FLASH MESSAGE TIME
displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or
any new target or message becomes active.
The
PUSHBTN 1 OFF TEXT
only if pushbutton element is in the "Latched" mode. The
PUSHBTN 1 ID
5
as "Normal" if the
PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into
event recorder.
The user-programmable pushbutton logic is shown below.
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
SETTING
PUSHBUTTON 1
FUNCTION
Disabled
Latched
OR
Self-Reset
SETTING
PUSHBTN 1 LOCAL
Off (FlexLogic operand)
SETTING
PUSHBTN 1 REMOTE
Off (FlexLogic operand)
SETTING
PUSHBTN 1 SET
Off (FlexLogic operand)
SETTING
PUSHBTN 1 RESET
Off (FlexLogic operand)
SETTING
PUSHBTN 1 AUTORST
Disabled
Enabled
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 2 ON
FLEXLOGIC OPERAND
OR
ANY PB ON
FLEXLOGIC OPERAND
PUSHBUTTON 3 ON
FLEXLOGIC OPERAND
*
PUSHBUTTON 12 ON
User-programmable pushbuttons require a type HP relay faceplate. If an HP type faceplate was ordered separately,
the relay order code must be changed to indicate the correct faceplate option. This can be done via EnerVista UR
NOTE
Setup with the Maintenance > Enable Pushbutton command.
5-42
is set to "Normal", the message programmed in the
PUSHBUTTON 1 ON
setting. After the flash time is expired, the default message or other active target message is
setting is linked to
PUSHBUTTON 1 OFF
setting is "High Priority" or "Normal".
PUSHBTN 1 MESSAGE
200
msec
0
msec
50
msec
0
msec
OR
50
msec
0
msec
OR
SETTING
PUSHBTN 1 AUTORST
DELAY
t
PKP
0
200
msec
0
msec
OR
INSTANTANEOUS RESET WILL BE EXECUTED IF ANY RELAY FRONT
PANEL BUTTON IS PRESSED OR ANY NEW TARGET OR MESSAGE
BECOMES ACTIVE.
Figure 5–6: USER-PROGRAMMABLE PUSHBUTTON LOGIC
L60 Line Phase Comparison Relay
operand is asserted, but not longer than time period specified
operand and will be displayed in conjunction with
PUSHBTN 1 OFF TEXT
Non Volatile Latch
OR
SET
LATCH
RST
OR
OR
SETTING
PUSHBTN 1 DROP-OUT
PUSH
TIME
0
t RST
INSTANTANEOUS
PUSHBUTTON 1 LED LOGIC
1. IF PUSHBUTTON 1 LED CONTROL IS SET TO OFF
FLEXLOGIC OPERAND
SETTING
PUSHBUTTON 1 ON
PUSHBTN 1 MESSAGE
Disable
2. IF PUSHBUTTON 1 LED CONTROL IS NOT SET TO OFF
High Priority
SETTING
Normal
PUSHBTN 1 LED CTL
ANY FLEXLOGIC
OPERAND
5 SETTINGS
and
PUSHBTN 1 ID
PUSHBTN 1 ON TEXT
message will be displayed
see PRODUCT SETUP
> DISPLAY PROPERTIES menu
SETTING
FLASH MESSAGE
TIME
LCD MESSAGE
0
ENGAGE MESSAGE
t RST
SETTING
PUSHBTN 1 ID TEXT
INSTANTANEOUS
RESET *
XXXXXXXXXX
PUSHBTN 1 OFF TEXT
XXXXXXXXXX
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
THE MESSAGE IS TEMPORARILY REMOVED IF
ANY KEYPAD BUTTON IS PRESSED. TEN(10)
SECONDS OF KEYPAD INACTIVITY RESTORES
THE MESSAGE
see PRODUCT SETUP
OR
> DISPLAY PROPERTIES menu
SETTING
LCD MESSAGE
FLASH MESSAGE
TIME
ENGAGE MESSAGE
0
t RST
SETTING
PUSHBTN 1 ID TEXT
XXXXXXXXXX
RESET *
PUSHBTN 1 ON TEXT
XXXXXXXXXX
PB1
LED
PB1
LED
GE Multilin
842021A1.DWG