GE L60 Instruction Manual page 201

Line phase comparison relay, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
POS SEQ di/dt FDH PICKUP: This setting controls pickup of the high set stage of the element used to control the trip
operation. Nominal current of the phase CT bank of the relay is 1pu.
POS SEQ di/dt FDH SEAL-IN: This setting defines seal-in time of the function. To equalize the response between all
terminals of the line, the timer is started at the rising edge of the raw di / dt condition. In this way, the fault detectors
reset approximately at the same time at all line terminals, regardless of responses of individual raw conditions poten-
tially different at different line terminals.
POS SEQ FDH SUPV: This setting provides seal-in control of the FDH function for the symmetrical external three-
phase faults starting as non-symmetrical defined by the
tance function should typically be assigned with this setting.
POS SEQ di/dt BLK: Note that the fault detector is hard-wired to the 87PC scheme. It can be disabled permanently
using the function setting, or blocked temporarily using this block setting. Select a FlexLogic™ operand that, if
asserted, should block this fault detector.
POS SEQ di/dt FD TARGET: This setting controls targets of the function. These targets operate independently from
the 87PC targets.
POS SEQ di/dt FD EVENTS: This setting controls event recording of the function. These events are logged indepen-
dently from the 87PC events.
SETTINGS
POS SEQ di/dt
FD FUNCTION:
Enabled = 1
POS SEQ di/dt
BLK:
Off = 0
FAST MEASUREMENTS
F1 PHASE CT BANK:
Pos-seq current, I_1
L1 PHASE CT BANK:
Pos-seq current, I_1
SETTINGS
POS SEQ FDH
SUPV:
Off = 0
Figure 5–42: POSITIVE-SEQUENCE CURRENT RATE OF CHANGE FAULT DETECTOR LOGIC
g) CHARGE CURRENT COMPENSATION
PATH: SETTINGS
GROUPED ELEMENTS
CHARGE CURRENT
COMPENSATION
MESSAGE
MESSAGE
MESSAGE
CHARGING CURRENT COMPENSATN: This setting enables/disables the charging current calculations and correc-
tions of the mixed current used as an operating quantity for fault detectors and square pulses. The voltage signals
used for charging current compensation are taken from source 3 or 4 assigned with the three-phase voltage bank on
the L5 voltage bank. As such, it's critical to ensure that three-phase line voltage is assigned to this source and voltage
bank settings are entered correctly. Half (or one-third for the three-terminal line, as defined by the
setting) of the line charging current is subtracted from the line current. The following diagram shows possible
SELECT
configurations.
GE Multilin
POS SEQ DI/DT FDH SEAL-IN
SETTINGS
POS SEQ di/dt
FDL PICKUP:
POS SEQ di/dt
FDH PICKUP:
RUN
> FDL PICKUP
| I_1 - I_1* |
(breaker 1)
>FDH PICKUP
> FDL PICKUP
| I_1 - I_1* |
(breaker 2)
> FDH PICKUP
(*) value delayed
by 0.5 cycle
PHASE COMPARISON ELEMENTS
CHARGE CURRENT
COMPENSATN: Disabled
CHARGE COMPENST BLK:
Off
POS SEQ CAPACITIVE
REACTANCE: 0.100 KΩ
ZERO SEQ CAPACITIVE
REACTANCE: 0.100 KΩ
L60 Line Phase Comparison Relay
5.5 GROUPED ELEMENTS
setting time. The overreaching dis-
Hardwired to the
TIMERS
87PC function
POS SEQ di/dt
FDL SEAL-IN:
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
0
87PC dI1/dt FDL OP
t
DPO
87PC dI1/dt FDH OP
POS SEQ di/dt
FDH SEAL-IN:
0
t
DPO
831801A1.CDR
CHARGE CURRENT COMPENSATION
Range: Disabled, Enabled
Range: any FlexLogic™ operand
Ω
Range: 0.100 to 65.535 k
in steps of 0.001
Ω
Range: 0.100 to 65.535 k
in steps of 0.001
5
87PC SCHEME
5-99

Advertisement

Table of Contents
loading

Table of Contents