CHAPTER 2: PRODUCT DESCRIPTION
Monitoring message count:
Alarm threshold:
TELEPROTECTION
Input points:
Remote devices:
Default states on loss of comms.:
Ring configuration:
Data rate:
CRC:

2.5.6 Power supply

LOW RANGE
Nominal DC voltage:
Minimum DC voltage:
Maximum DC voltage:
Voltage loss hold-up:
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
Minimum DC voltage:
Maximum DC voltage:
Nominal AC voltage:
Minimum AC voltage:
Maximum AC voltage:
Voltage loss hold-up:
ALL RANGES
Volt withstand:
Power consumption:
INTERNAL FUSE
Ratings:
Low range power supply:
High range power supply:
Interrupting capacity:
AC:
DC:

2.5.7 Outputs

FORM-A RELAY
Make and carry for 0.2 s:
Carry continuous:
Break (DC inductive, L/R = 40 ms):
Voltage
Current
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
10 to 10000 in steps of 1
1 to 1000 in steps of 1
16
3
On, Off, Latest/Off, Latest/On
No
64 or 128 kbps
32-bit
24 to 48 V
20 V
75 V for SL power supply module
200 ms duration at maximum load
125 to 250 V
88 V
300 V
100 to 240 V at 50/60 Hz
88 V at 25 to 100 Hz
265 V at 25 to 100 Hz
200 ms duration at maximum load
2 × Highest Nominal Voltage for 10 ms
typical = 15 to 20 W/VA
maximum = 45 W/VA
contact factory for exact order code consumption
8 A / 250 V
4 A / 250 V
100 000 A RMS symmetrical
10 000 A
30 A as per ANSI C37.90
6 A
SPECIFICATIONS
2
2-31