GE G30 Instruction Manual page 399

Generator protection system 7.4x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
where
T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
V
= pickup level
pickup
At 0% of pickup, the operating time equals the
5.7.10.2 Phase undervoltage (ANSI 27P, IEC PTUV)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  PHASE UNDERVOLTAGE1(3)
 PHASE
 UNDERVOLTAGE1
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-117: Inverse time undervoltage curves
PHASE UNDERVOLTAGE DELAY
PHASE UV1
FUNCTION: Disabled
PHASE UV1 SIGNAL
SOURCE: SRC 1
PHASE UV1 MODE:
Phase to Ground
PHASE UV1
PICKUP: 1.000 pu
PHASE UV1
CURVE: Definite Time
PHASE UV1
DELAY: 1.00 s
PHASE UV1 MINIMUM
VOLTAGE: 0.100 pu
PHASE UV1 BLOCK:
Off
PHASE UV1
TARGET: Self-reset
PHASE UV1
EVENTS: Disabled
GROUPED ELEMENTS
setting.
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Phase to Ground, Phase to Phase
Range: 0.004 to 3.000 pu in steps of 0.001
Range: Definite Time, Inverse Time
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.000 to 3.000 pu in steps of 0.001
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-225

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents