GE G30 Instruction Manual page 278

Generator protection system 7.4x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

PRODUCT SETUP
3.
All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and
monitoring features. However, the LED control mechanism accepts all the changes to LED states generated by the relay
and stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting
from relay response during testing. The reset pushbutton does not clear any targets when the LED Test is in progress.
A dedicated FlexLogic operand,
the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the
setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is
executed.
5
Application example 1
Assume one needs to check if any of the LEDs is "burned" through user-programmable pushbutton 1. Apply the following
settings.
Configure user-programmable pushbutton 1 by making the following entries in the
PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the
PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST
5-104
PROGRESS, is set for the duration of the test. When the test sequence is initiated,
LED TEST IN
Figure 5-42: LED test sequence
menu. (The option does not display when not purchased.)
: "Self-reset"
: "0.10 s"
SETTINGS  PRODUCT SETUP  USER-
menu:
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
LED TEST CONTROL
SETTINGS 