GE G30 Instruction Manual page 407

Generator protection system 7.4x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
GROUPED ELEMENTS
T = Operating Time
TDM = Time Delay Multiplier (delay in seconds)
V = fundamental RMS value of voltage (pu)
F = frequency of voltage signal (pu)
Pickup = volts-per-hertz pickup setpoint (pu)
The figure shows the volts/hertz inverse A curves.
Figure 5-125: Volts-per-hertz curves, inverse curve A
5
Inverse curve B
The curve for the Volts/Hertz Inverse Curve B shape is derived from the formula:
Eq. 5-55
where
T = Operating Time
TDM = Time Delay Multiplier (delay in sec.)
V = fundamental RMS value of voltage (pu)
F = frequency of voltage signal (pu)
Pickup = volts-per-hertz pickup setpoint (pu)
The figure shows the volts/hertz inverse B curves.
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5-233