G30 Generator Protection System
Chapter 10: Theory of operation
Theory of operation
This chapter outlines advanced information on operation.
10.1 Saturation detector
10.1.1 CT saturation detection
The saturation detector of the G30 takes advantage of the fact that any CT operates correctly for a short period of time,
even under very large primary currents that would subsequently cause a very deep saturation. As a result, in the case of
an external fault, the differential current stays very low during the initial period of linear operation of the CTs while the
restraining signal develops rapidly. Once one or more CTs saturate, the differential current increases. The restraining signal,
however, yields by at least a few milliseconds. During internal faults, both the differential and restraining currents develop
simultaneously. This creates characteristic patterns for the differential - restraining trajectory, as shown.
Figure 10-1: CT saturation detection internal and external fault patterns
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
10-1