GE G30 Instruction Manual page 213

Generator protection system 7.4x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
5.3.4.10 DNP protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL
 DNP PROTOCOL
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
 DNP CHANNELS
DNP ADDRESS:
1
 DNP NETWORK
 CLIENT ADDRESSES
DNP TCP/UDP PORT
NUMBER(20000): 20000
DNP UNSOL RESPONSE
FUNCTION: Disabled
DNP UNSOL RESPONSE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MAX RETRIES: 10
DNP UNSOL RESPONSE
DEST ADDRESS: 1
DNP CURRENT SCALE
FACTOR: 1
DNP VOLTAGE SCALE
FACTOR: 1
DNP POWER SCALE
FACTOR: 1
DNP ENERGY SCALE
FACTOR: 1
DNP PF SCALE
FACTOR: 1
DNP OTHER SCALE
FACTOR: 1
DNP CURRENT DEFAULT
DEADBAND: 30000
DNP VOLTAGE DEFAULT
DEADBAND: 30000
DNP POWER DEFAULT
DEADBAND: 30000
DNP ENERGY DEFAULT
DEADBAND: 30000
DNP PF DEFAULT
DEADBAND: 30000
DNP OTHER DEFAULT
DEADBAND: 30000
DNP TIME SYNC IIN
PERIOD: 1440 min
DNP MESSAGE FRAGMENT
SIZE: 240
DNP OBJECT 1
DEFAULT VARIATION: 2
See below
Range: 0 to 65535 in steps of 1
See below
Range: 0 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 60 s in steps of 1
Range: 1 to 255 in steps of 1
Range: 0 to 65519 in steps of 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 1 to 10080 min. in steps of 1
Range: 30 to 2048 in steps of 1
Range: 1, 2
PRODUCT SETUP
5
5-39