CHAPTER 5: SETTINGS
Operand type
State
RxGOOSE Boolean
On
Virtual Input
On
Virtual Output
On
The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.
Table 5-21: G30 FlexLogic operands
Operand type
Operand syntax
CONTROL
CONTROL PUSHBTN 1 ON
PUSHBUTTONS
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
CYBERSENTRY
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
DIRECT DEVICES
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIR IO CH1 CRC ALARM
DIRECT INPUT/
OUTPUT CHANNEL
MONITORING
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
ELEMENT:
3RD HARM NTRL UV PKP
Third harmonic
3RD HARM NTRL UV OP
neutral undervoltage
3RD HARM NTRL UV DPO
ELEMENT:
ACCDNT ENRG ARMED
Accidental
ACCDNT ENRG DPO
energization
ACCDNT ENRG OP
ELEMENT:
AUX OV1 PKP
Auxiliary overvoltage
AUX OV1 DPO
AUX OV1 OP
AUX OV2
ELEMENT:
AUX UV1 PKP
Auxiliary
AUX UV1 DPO
undervoltage
AUX UV1 OP
AUX UV2 to 3
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Example of format
Characteristics
[Input Is '1' (= ON) if...]
RxGOOSE Boolean 1 On
The RxGOOSE Boolean is presently in the ON state
Virt Ip 1 On
The virtual input is presently in the ON state
Virt Op 1 On
The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
Operand description
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
Third harmonic neutral undervoltage element has picked up
Third harmonic neutral undervoltage element has operated
Third harmonic neutral undervoltage element has dropped out
The accidental energization element is armed
The accidental energization element has dropped out
The accidental energization element has operated
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Same set of operands as shown for AUX OV1
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
Same set of operands as shown for AUX UV1
FLEXLOGIC
5
5-157