CHAPTER 5: SETTINGS
In our example, the following phase and zero-sequence compensation equations would be used:
For Winding 1:
For Winding 2:
5.5.4.7 Magnitude, phase, angle, and zero-sequence compensation calculations
Complete magnitude, phase angle, and zero sequence compensation is as follows:
where
c
c
c
I
[w], I
[w], and I
[w] = magnitude, phase, and zero-sequence compensated winding w phase currents
A
B
C
M [w] = magnitude compensation factor for winding w (see previous sections)
p
c
c
I
[w], I
[w], and I
[w] = phase and zero sequence compensated winding w phase currents (see earlier)
A
B
C
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
c
p
I
[w] = M [w] x I
[w], where w = 1, 2
A
A
c
p
I
[w] = M [w] x I
[w], where w = 1, 2
B
B
c
p
I
[w] = M [w] x I
[w], where w = 1, 2
C
C
SYSTEM SETUP
5
Eq. 5-18
Eq. 5-19
Eq. 5-20
Eq. 5-21
Eq. 5-22
5-139