Outputs; Power Supply - GE 735 Instruction Manual

Feeder protection relay
Table of Contents

Advertisement

1 INTRODUCTION
TRIP, AUX TRIP OUTPUT RELAYS
VOLTAGE
DC Resistive
30 V DC
125 V DC
250 V DC
DC Inductive,
30 V DC
L/R = 40 mS
125 V DC
250 V DC
AC Resistive
120 V AC
250 V AC
AC Inductive
120 V AC
PF = 0.4
250 V AC
Configuration:
Form A NO
Contact Material:
Silver Alloy
SERVICE, PICKUP/CAUSE OF TRIP OUTPUT RELAYS
VOLTAGE
DC Resistive
30 V DC
125 V DC
250 V DC
DC Inductive,
30 V DC
L/R = 40 mS
125 V DC
250 V DC
AC Resistive
120 V AC
250 V AC
AC Inductive
120 V AC
PF = 0.4
250 V AC
Configuration:
Form C NO/NC
Contact Material:
Silver Alloy
CONTROL POWER
DC supply:
HI: 125 V DC, 250 V DC nominal
LO: 48 V DC nominal
Range:
HI: 90 to 300 VDC, 70 to 265 V AC
LO: 20 to 60 V DC, 20 to 48 V AC
Power:
nominal 10W, maximum 25W
GE Power Management
MAKE/CARRY
CONTINUOUS
0.2 S
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
20 A
80 A
MAKE/CARRY
CONTINUOUS
0.2 S
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
10 A
30 A
735/737 Feeder Protection Relay
1.3 SPECIFICATIONS
BREAK
MAX LOAD
16 A
480 W
0.8 A
100 W
0.4 A
100 W
5 A
150 W
0.3 A
375 W
0.2 A
50 W
20 A
2400 VA
20 A
5000 VA
8 A
960 VA
7 A
1750 VA
BREAK
MAX LOAD
10 A
300 W
0.5 A
62.5 W
0.3 A
75 W
5 A
150 W
0.25 A
31.3 W
0.15 A
37.5 W
10 A
2770 VA
10 A
2770 VA
4 A
480 VA
3 A
750 VA

1.3.4 POWER SUPPLY