CGCOMMUNICATIONS GUIDE
ATTRIBUTE
4.13

DeviceNet Data Formats

369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 6 of 6)
BYTES
DESCRIPTION
201, 202 (low, high)
Starts timer [2]
203, 204 (low, high)
Starts timer [3]
205, 206 (low, high)
Starts timer [4]
207, 208 (low, high)
Starts timer [5]
209, 210 (low, high)
Time between starts timer
211, 212 (low, high)
Restart block timer
213, 214 (low, high)
Start inhibit timer
FORMAT
VALUE
F167
Network status: unsigned 16 bit integer
0
1
2
3
F168
Connection status: unsigned 16 bit integer
0
1
2
3
4
5
F170
DeviceNet baud rate: unsigned 16 bit integer
0
1
2
F172
Motor status: Unsigned 8 bit integer
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bits 5 to 7
F173
Digital input status: unsigned 8 bit integer
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
F174
Output relay status: unsigned 8 bit integer
DEVICENET PROTOCOL
LENGTH
FORMAT
16 bits
UINT
minutes
16 bits
UINT
minutes
16 bits
UINT
minutes
16 bits
UINT
minutes
16 bits
UINT
minutes
16 bits
UINT
seconds
16 bits
UINT
minutes
NAME/DESCRIPTION
Power off / Not online
Online, Connected
Link failure
Not defined
Nonexistent
Configuring
(Not used)
Established
Timed out
Deferred delete
125 kbps
250 kbps
500 kbps
Stopped
Starting
Running
Overloaded
Tripped
Reserved
Access Switch Status
0 = Open, 1= Closed
Speed Switch Status
0 = Open, 1= Closed
Spare Switch Status
0 = Open, 1= Closed
Differential Switch Status
0 = Open, 1= Closed
Emergency Switch status
0 = Open, 1= Closed
Reset Switch Status
0 = Open, 1= Closed
Reserved
Reserved
VALUE/UNIT