369 Relay Profibus-Dp Diagnostics; Diagnostic Bytes 1 Through 7 - GE 369 Communications Manual

Motor management relay
Hide thumbs Also See for 369:
Table of Contents

Advertisement

CGCOMMUNICATIONS GUIDE
OFFSET
202
204
206
208
210
212
214
216
218
2.4

369 Relay Profibus-DP Diagnostics

369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Table CG–1: Profibus Input Data (Sheet 4 of 4)
CYCLIC DATA
LENGTH
(ACTUAL VALUES)
(BYTES)
Last pre–trip Vca
2
Last pre–trip Van
2
Last pre–trip Vbn
2
Last pre–trip Vcn
2
Last pre–trip Frequency
2
Last pre–trip KiloWatts
2
Last pre–trip KiloVAR
2
Last pre–trip KiloVA
2
Last pre–trip PowerFactor
2
The 369 Motor Management Relay supports both slave mandatory (6 bytes system-wide
standardized) and slave specific diagnostic data. If the diagnostics are considered high
priority, the PLC/host program will be informed of the fault (alarm or trip) and can call a
special error routine.
Diagnostic bytes 1 through 6 represent standard diagnostic data and are formatted as
follows.
1
2
3
4
5
6
The extended diagnosis for the relay is composed of 26 bytes (bytes 7 to 32) and contains
diagnostic information according to the following table.
BIT
0 to 7
0
1
MINIMUM
MAXIMUM
VALUE
HEX
VALUE
0
0000
65000
0
0000
65000
0
0000
65000
0
0000
65000
0
0000
12000
8300
32000
32000
8300
32000
32000
0
0000
50000
–99
FF9D
100
Table CG–2: Diagnostic bytes 1 through 7
BYTE
DESCRIPTION
Station Status 1
Station Status 2
Station Status 3
Diagnostic Master Address
Identification Number (High Byte)
Identification Number (Low Byte)
Table CG–3: Profibus Diagnostics (Sheet 1 of 7)
BYTE
7
Number of Diagnostic Bytes
8
SinglePhasingTrip
8
SpareSwitchTrip
PROFIBUS-DP COMMUNICATIONS
STEP
UNITS FORMAT
VALUE
CODE
HEX
FDE8
1
V
F1
FDE8
1
V
F1
FDE8
1
V
F1
FDE8
1
V
F1
2EE0
1
Hz
F3
7D00
1
kW
F4
7D00
1
kvar
F4
C350
1
kVA
F1
0064
1
F21
FUNCTION
DEFAULT
0
0
0
0
0
0
0
0
0
CG9