PROFIBUS-DPV1 COMMUNICATIONS

3
Profibus-DPV1 Communications
3.1

369 Relay Profibus-DPV1 Parameterization

CG16

If programmed as Unlatched:

Any programmed output relays for this feature will be activated until communication is
active. Once communication is active, the trip condition will be cleared and the assigned
output relays will automatically de-activate.
The setpoints associated with this feature are:
1.
Profibus Loss of Comms Enable
2.
Profibus Loss of Comms Delay
3.
Assigned Profibus Loss of Comms Relay
Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more
information on these setpoints.
The 369 Motor Management Relay supports mandatory parametrization as well as three
bytes of user parameter data necessary for DPV1 devices. The relay keeps its user
parameter data/setpoints in a non-volatile memory and does not require device related
parametrization during startup of the DP/V1 master, with the exception of the DPV1 Enable
parameter. To enable the DPV1 acyclical functionality, the DPV1 parameter must be set to
"Enable" when configuring the device in your master using the GSD file.
The EnerVista 369 Setup software is the best tool for editing user parametrization
(setpoints) of the 369 Relay device.
FIGURE CG–2: User Parameter Setup – Enable DPV1
CGCOMMUNICATIONS GUIDE
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE