CGCOMMUNICATIONS GUIDE
3.5
369 Relay Profibus Diagnostics
3.6
369 Relay Profibus-DPV1 Acyclical Communication
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
A slave configuration example for 4 bytes of input data and 2 bytes of output data is
shown below.
FIGURE CG–5: Slave Configuration Example – 4 Bytes of Input Data, 2 bytes of Output Data
OFFSET
CYCLIC DATA
(ACTUAL VALUES)
0
Force Output Relays
The diagnostic data available for the Profibus-DPV1 option matches Table CG–3: Profibus
Diagnostics on page CG–9. When no diagnostic information is available and the master
initiates a diagnostics read, the six slave mandatory bytes are read.
The following items have been made available through Profibus-DPV1 acyclical
communication. Data is addressed through the use of "slot and index" addressing. Three
parameters are required to read or write data from the 369 Relay using a Profibus-DPV1
master:
1.
Slot number
2.
Index number
3.
Data length (number of 16-bit words)
Table CG–4: Profibus Output Data
LENGTH
MINIMUM
(BYTES)
VALUE
2
0
PROFIBUS-DPV1 COMMUNICATIONS
MAXIMUM
HEX
VALUE
HEX
0
15
F
FORMAT
CODE
F141
CG19