Memory Map Data Formats - GE 489 Communications Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

ADDR
302A
Hottest Other RTD Temperature
302B
Hottest Ambient RTD Number
302C
Hottest Ambient RTD Temperature
302D
Analog Input 1
302F
Analog Input 2
3031
Analog Input 3
3033
Analog Input 4
3035
Phase A Neutral Current
3037
Phase B Neutral Current
3039
Phase C Neutral Current
30E0
Hottest Stator RTD Temperature
30E1
Hottest Bearing RTD Temperature
30E2
Hottest Other RTD Temperature
30E3
Hottest Ambient RTD Temperature
30E5
Neutral Voltage (Fundamental)
30E7
Neutral Voltage (3rd Harmonic)
30E9
Vab/Iab
30EA
Vab/Iab Angle
WAVEFORM MEMORY SETUP
30F0
Waveform Memory Trigger Date
30F2
Waveform Memory Trigger Time
30F4
Frequency During Trace Acquisition
30F5
Waveform Memory Channel Selector (Holding Register)
30F6
Waveform Trigger Selector
30F7
Waveform Trigger Cause (Read-only)
30F8
Number of Samples per Trace
30F9
Number of Waveform Captures Taken
WAVEFORM MEMORY SAMPLES
3100
First Waveform Memory Sample
3700
Last Waveform Memory Sample
1, 2, 3
See Table footnotes on page page 42
*. A Value of 65535 indicates 'Never'
. A value of 0xFFFF indicates "no measurable value".
. Maximum value turns feature 'Off'
CG.3.8 Memory Map Data Formats
42
Table CG–1: 489 Memory Map (Sheet 30 of 30)
Name
The data formats used in the Modbus memory map are shown below.
Table CG–2: Data Formats (Sheet 1 of 14)
CODE
16 bits
F1
Example: 1234 stored as 1234
16 bits
F2
Example: 123.4 stored as 1234
16 bits
F3
Example: 12.34 stored as 1234
16 bits
F4
Example: –1234 stored as –1234 (i.e. 64302)
RANGE
STEP
–50 to 250
1
1 to 12
1
–50 to 250
1
–50000 to 50000
1
–50000 to 50000
1
–50000 to 50000
1
–50000 to 50000
1
0 to 999999
1
0 to 999999
1
0 to 999999
1
–50 to 250
1
–50 to 250
1
–50 to 250
1
–50 to 250
1
0 to 250000
1
0 to 250000
1
0 to 65535
1
0 to 359
1
N/A
N/A
N/A
N/A
0 to 12000
1
0 to 9
1
1 to 65535
1
0 to 139
1
1 to 1536
-
0 to 65535
1
–32767 to 32767
1
–32767 to 32767
1
TYPE
DEFINITION
UNSIGNED VALUE
UNSIGNED VALUE,
1 DECIMAL PLACE
UNSIGNED VALUE,
2 DECIMAL PLACES
2's COMPLEMENT SIGNED VALUE
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
UNITS
FORMAT
DEFAULT
°C
F4
0
F1
1
°C
F4
0
Units
F12
0
Units
F12
0
Units
F12
0
Units
F12
0
Amps
F12
0
Amps
F12
0
Amps
F12
0
°F
F4
0
°F
F4
0
°F
F4
0
°F
F4
0
Volts
F10
0
Volts
F10
0
ohms s
F1
0
°
F1
0
N/A
F18
N/A
N/A
F19
N/A
Hz
F3
0
N/A
F214
0
N/A
F1
0
N/A
F134
0
-
F1
N/A
N/A
F1
0
-
F4
0
-
F4
0