DEVICENET PROTOCOL
4.8

DeviceNet Connection Object (class code 05h)

CG26
Assembly object, Class code 04h, Instance 96h, Attributes.
ATTRIBUTE
ACCESS
03h
Set
BIT POSITION
0
1
2
3
4
5
6
7
For execution of DeviceNet control commands, one of the switch assignments should be
set to "DeviceNet Control" and be closed.
The motor start command energizes the output relay set with the
setpoint. The motor stop command energizes the trip relay. The fault reset command
resets the latched trip and alarm conditions, provided the cause of alarm/trip is removed.
The commands are executed continuously as long as the control bits are high. When two
or more commands are executed simultaneously, only one will be executed. The command
hierarchy for execution is given below.
1. Motor stop
2. Fault reset
3. Motor start
The corresponding command bit should be high for more than 500 ms to execute the
command.
The connection objects manage the characteristics of each communication connection.
There are two instances of the connection object in the device: explicit connection (<50 ms
response) and input/output connection poll (<10 ms response).
Connection Object, Class Code 05h, Services:
CODE
NAME AND DESCRIPTION OF SERVICES AVAILABLE TO THIS OBJECT
0x05
Reset the connection - restart timer
0x0E
Get_Attribute_Single: Returns the contents of the given attribute.
0x10
Set_Attribute_Single: Sets the contents of the given attribute
NAME/DESCRIPTION
Control byte
DATA FORMATS, CONTROL BYTE
NAME
Motor start
Motor stop
Fault reset
Reserved
Reserved
Reserved
Reserved
Reserved
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
CGCOMMUNICATIONS GUIDE
DATA TYPE
VALUE
1 byte
see below
VALUE
0, 1
0, 1
0, 1
---
---
---
---
---
START CONTROL RELAY