CGCOMMUNICATIONS GUIDE
4.2

Poll Data

369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
The EDS file for use with a DeviceNet master can be generated using the EnerVista 369
Setup program. The EDS file differs depending on which Poll Group is selected, and by the
amount of data being returned for the User-Defined Poll Data. Note that only one version
of the EDS file may be used for any one DeviceNet master.
The 369 Motor Management Relay supports following DeviceNet object classes.
Table CG–7: DeviceNet Object Classes
CLASS
01h
02h
03h
04h
05h
2Bh
A0h
A1h
B0h
The polling function consumes one byte of control data and produces data as per Poll Data
Group 1, Poll Data Group 2, or the User-Defined poll data. The control data format is as
follows:
Bit Position
0
1
2
3
4
5
6
7
For execution of DeviceNet control commands, one of the switch assignments should be
set to "DeviceNet Control" and be closed.
The motor start command energizes the output relay set with the START CONTROL RELAY
setpoint. The motor stop command energizes the trip relay. The fault reset command
resets the latched trip and alarm conditions, provided the cause of alarm/trip is removed.
Object
Identity
Message Router
DeviceNet
Assembly
Connection
Acknowledge Handler
IO data Input Mapping
IO data Output Mapping
Parameter Data input Mapping
Name
Motor Start
0.1
Motor Stop
0.1
Fault Reset
0.1
Reserved
-
Reserved
-
Reserved
-
Reserved
-
Reserved
-
DEVICENET PROTOCOL
Value
CG21