Profibus Input Data - GE 369 Communications Manual

Motor management relay
Hide thumbs Also See for 369:
Table of Contents

Advertisement

PROFIBUS-DP COMMUNICATIONS
OFFSET
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
CG6
Table CG–1: Profibus Input Data (Sheet 1 of 4)
CYCLIC DATA
LENGTH
(ACTUAL VALUES)
(BYTES)
MotorStatus
2
TC_Used
2
Time_to_Trip
2
OverloadLT
2
StartsHourLT[5]
2
TimeBetween StartsLT
2
RestartBlock LT
2
StartInhibitLT
2
AccessSwitch Status
2
SpeedSwitch Status
2
SpareSwitch Status
2
DiffSwitch Status
2
EmergencySwitch status
2
ResetSwitch Status
2
TripRelayStatus
2
AlarmRelayStatus
2
Aux1RelayStatus
2
Aux2RelayStatus
2
Ia
2
Ib
2
Ic
2
AveragePhaseCurrent
2
MotorLoad
2
CurrentUnbalance
2
U/B Biased Motor Load
2
GroundCurrent
2
Vab
2
Vbc
2
Vca
2
Van
2
Vbn
2
Vcn
2
AvgLineVoltage
2
MINIMUM
MAXIMUM
VALUE
HEX
VALUE
HEX
0
0000
4
0004
0
0000
100
0064
–1
FFFF
65500
FFDC
0
0000
50000
C350
0
0000
60
003C
0
0000
500
01F4
0
0000
50000
C350
0
0000
60
003C
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
1
0001
0
0000
65535
FFFF
0
0000
65535
FFFF
0
0000
65535
FFFF
0
0000
65535
FFFF
0
0000
2000
07D0
0
0000
100
0064
0
0000
2000
07D0
0
0000
50000
C350
0
0000
65000
FDE8
0
0000
65000
FDE8
0
0000
65000
FDE8
0
0000
65000
FDE8
0
0000
65000
FDE8
0
0000
65000
FDE8
0
0000
65000
FDE8
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
CGCOMMUNICATIONS GUIDE
STEP
UNITS FORMAT
DEFAULT
VALUE
CODE
1
F133
0
1
%
F1
0
1
s
F20
–1
1
s
F1
0
1
min
F1
0
1
min
F1
0
1
s
F1
0
1
min
F1
0
1
F131
0
1
F131
0
1
F131
0
1
F131
0
1
F131
0
1
F131
0
1
N/A
F150
2
1
N/A
F150
2
1
N/A
F150
2
1
N/A
F150
2
1
A
F1
0
1
A
F1
0
1
A
F1
0
1
A
F1
0
1
xFLA
F3
0
1
%
F1
0
1
xFLC
F3
0
1
A
F23
0
1
V
F1
0
1
V
F1
0
1
V
F1
0
1
V
F1
0
1
V
F1
0
1
V
F1
0
1
V
F1
0