DEVICENET PROTOCOL
ATTRIBUTE
1Dh
ACTUAL VALUES
continued
1Dh
ACTUAL VALUES
continued
CG34
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 5 of 6)
BYTES
DESCRIPTION
97,98 (low, high)
Current demand
99,100 (low, high)
Real power demand
101,102 (low, high)
Reactive power demand
103, 104 (low, high)
Apparent power demand
105, 106 (low, high)
Peak current demand
107, 108 (low, high)
Peak real power demand
Peak reactive power
109, 110 (low, high)
demand
Peak apparent power
111,112 (low, high)
demand
113,114 (low, high)
Learned acceleration time
115,116 (low, high)
Learned starting current
117,118 (low, high)
Learned starting capacity
Learned running cool time
119,120 (low, high)
constant
Learned stopped cool time
121,122 (low, high)
constant
123,124 (low, high)
Last starting capacity
Learned unbalance k-
125,126 (low, high)
factor
127,128 (low, high)
Number of starts
129,130 (low, high)
Number of restarts
131,132 (low, high)
Digital counter
133,134 (low, high)
Motor running Hours
135,136 (low, high)
Cause of last trip
137 to 140 (low, high)
Last trip date
141 to 144 (low, high)
Last trip time
145, 146 (low, high)
Last pre-trip Ia
147, 148 (low, high)
Last pre-trip Ib
149, 150 (low, high)
Last Pre-trip Ic
151, 152 (low, high)
Last Pre-trip Ig
153, 154 (low, high)
Last pre-trip motor load
155, 156 (low, high)
Last pre-trip unbalance
Last pre-trip local hottest
157, 158 (low, high)
stator RTD
Last pre-trip local hottest
159, 160 (low, high)
stator RTD temperature
161, 162 (low, high)
Last pre-trip Vab
163, 164 (low, high)
Last pre-trip Vbc
165, 166 (low, high)
Last pre-trip Vca
167, 168 (low, high)
Last pre-trip Van
169, 170 (low, high)
Last pre-trip Vbn
171, 172 (low, high)
Last pre-trip Vcn
173, 174 (low, high)
Last pre-trip frequency
175, 176 (low, high)
Last pre-trip kilowatts
177, 178 (low, high)
Last pre-trip kvar
179, 180 (low, high)
Last pre-trip KVA
181, 182 (low, high)
Last pre-trip power factor
183 to 188
Trip diagnostic data
189 to 196
Alarm diagnostic data
197, 198 (low, high)
Overload lockout timer
199, 200 (low, high)
Starts timer [1]
CGCOMMUNICATIONS GUIDE
LENGTH
FORMAT
16 bits
UINT
16 bits
UINT
16 bits
F4
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
F4
16 bits
UINT
16 bits
F2
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
F134
32 bits
F18
32 bits
F19
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
F2
16 bits
F3
16 bits
UINT
16 bits
UINT
16 bits
F4
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
UINT
16 bits
F3
16 bits
F4
16 bits
F4
16 bits
UINT
16 bits
F21
48 bits
F176
64 bits
F177
16 bits
UINT
16 bits
UINT
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
VALUE/UNIT
A
kW
kvar
kVA
A
kW
kvar
kVA
× 0.1 seconds
A
%
minutes
minutes
%
--
--
--
--
hours
--
--
--
A
A
A
× 0.1 A
× 0.01 FLA
%
---
°C
volts
volts
volts
volts
volts
volts
× 0.01 Hz
kW
kvar
kVA
× 0.01 PF
minutes
minutes