Rrtd 1 – Rtd #11; Rrtd 1 – Rtd #12; Rrtd 1 – Open Rtd Alarm / Rrtd 1 - Short/Low Temperature Rtd Alarm; Rrtd 2 – Rtd #1 - GE 369 Communications Manual

Motor management relay
Hide thumbs Also See for 369:
Table of Contents

Advertisement

MEMORY MAP
CG78
Table CG–10: MEMORY MAP (Sheet 33 of 57)
ADDR
DESCRIPTION
(hex)
2140
RRTD 1 - RTD #11 Application
2141
RRTD 1 - RTD #11 High Alarm
2142
RRTD 1 - RTD #11 High Alarm Relays
2143
RRTD 1 - RTD #11 High Alarm Level
2144
RRTD 1 - RTD #11 Alarm
2145
RRTD 1 - RTD #11 Alarm Relays
2146
RRTD 1 - RTD #11 Alarm Level
Record RRTD 1 - RTD #11 Alarms as
2147
Events
2148
RRTD 1 - RTD #11 Trip
2149
Enable RRTD 1 - RTD #11 Trip Voting
214A
RRTD 1 - RTD #11 Trip Relays
214B
RRTD 1 - RTD #11 Trip Level
214C
RRTD 1 - RTD #11 RTD Type
2150
First Character of RRTD 1 - RTD #11 Name 32
2153
8th Character of RRTD 1 - RTD #11 Name 32
...
Reserved
2160
RRTD 1 - RTD #12 Application
2161
RRTD 1 - RTD #12 High Alarm
2162
RRTD 1 - RTD #12 High Alarm Relays
2163
RRTD 1 - RTD #12 High Alarm Level
2164
RRTD 1 - RTD #12 Alarm
2165
RRTD 1 - RTD #12 Alarm Relays
2166
RRTD 1 - RTD #12 Alarm Level
Record RRTD 1 - RTD #12 Alarms as
2167
Events
2168
RRTD 1 - RTD #12 Trip
2169
Enable RRTD 1 - RTD #12 Trip Voting
216A
RRTD 1 - RTD #12 Trip Relays
216B
RRTD 1 - RTD #12 Trip Level
216C
RRTD 1 - RTD #12 RTD Type
2170
First Character of RRTD 1 - RTD #12 Name 32
2173
8th Character of RRTD 1 - RTD #12 Name 32
...
Reserved
2180
RRTD A - Open RTD Alarm
2181
RRTD A - Assign Alarm Relays
2182
RRTD A - Open RTD Alarm Events
2183
RRTD A - Short / Low Temp RTD Alarm
2184
RRTD A - Assign Alarm Relays
2185
RRTD A - Short / Low Temp Alarm Events
...
Reserved
2200
RRTD 2 - RTD #1 Application
2201
RRTD 2 - RTD #1 High Alarm
2202
RRTD 2 - RTD #1 High Alarm Relays
2203
RRTD 2 - RTD #1 High Alarm Level
2204
RRTD 2 - RTD #1 Alarm
2205
RRTD 2 - RTD #1 Alarm Relays
2206
RRTD 2 - RTD #1 Alarm Level
2207
Record RRTD 2 - RTD #1 Alarms as Events 0
2208
RRTD 2 - RTD #1 Trip
2209
Enable RRTD 2 - RTD #1 Trip Voting
220A
RRTD 2 - RTD #1 Trip Relays
220B
RRTD 2 - RTD #1 Trip Level
MIN.
MAX.
RRTD 1 – RTD #11
0
4
0
2
0
7
1
200
0
2
0
7
1
200
0
1
0
2
0
13
0
7
1
200
0
3
127
127
RRTD 1 – RTD #12
0
4
0
2
0
7
1
200
0
2
0
7
1
200
0
1
0
2
0
13
0
7
1
200
0
3
127
127
RRTD 1 – OPEN RTD ALARM
0
2
0
7
0
1
RRTD 1 – SHORT/LOW TEMPERATURE RTD ALARM
0
2
0
7
0
1
-
-
RRTD 2 – RTD #1
0
4
0
2
0
7
1
200
0
2
0
7
1
200
1
0
2
0
13
0
7
1
200
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
CGCOMMUNICATIONS GUIDE
STEP
UNITS
FORMAT
VALUE
CODE
1
-
F121
1
-
F115
1
-
F113
1
°C
F1
1
-
F115
1
-
F113
1
°C
F1
1
-
F103
1
-
F115
1
-
F122
1
-
F111
1
°C
F1
1
-
F120
1
-
F1
1
-
F1
1
-
F121
1
-
F115
1
-
F113
1
°C
F1
1
-
F115
1
-
F113
1
°C
F1
1
-
F103
1
-
F115
1
-
F122
1
-
F111
1
°C
F1
1
-
F120
1
-
F1
1
-
F1
1
-
F115
1
-
F113
1
-
F103
1
-
F115
1
-
F113
1
-
F103
-
-
-
1
-
F121
1
-
F115
1
-
F113
1
°C
F1
1
-
F115
1
-
F113
1
°C
F1
1
-
F103
1
-
F115
1
-
F122
1
-
F111
1
°C
F1
FACTORY
DEFAULT
0
0
2
130
0
1
130
0
0
1
1
130
0
'R'
" "
0
0
2
130
0
1
130
0
0
1
1
130
0
'R'
" "
0
1
0
0
1
0
-
0
0
2
130
0
1
130
0
0
1
1
130

Hide quick links: