These settings are kept in a separate area of the SRAM database and will be retained following the sending
of a configuration to the FloBoss S600 unit.
When any Modbus slave configuration builder has an address of zero specified, the Modbus port will be
configured with the address entered here. This is typically used when the same configuration file is loaded
into multiple FloBoss S600 flow computers on the same Modbus network; thus, giving each FloBoss S600
a unique node address.
To define the Modbus network addresses:
Select NETWORK SETUP from the Startup menu.
1.
Select the Modbus Address option.
2.
Enter the address value (a maximum value of 247 is permitted).
3.
If the Modbus address has been changed, restart the FloBoss S600 for the change to take place.
Before establishing an Ethernet LAN connection (for host communications, local operator
communications, or web server access), you will need to verify and/or define the TCP/IP Address.
To define the Ethernet LAN network addresses:
1.
Select NETWORK SETUP from the Startup menu.
Select the TCP/IP Interface option.
2.
Enter the TCP/IP Gateway Address and subnet mask for the selected infterface (1 or 2).
3.
Network I/F 1 is for the standard Ethernet port. Network I/F 2 is for the Dual Ethernet port.
Rev Sep/04
Startup
7-4