Installation And Removal Of The Boards - Emerson FLOBOSS S600 Instruction Manual

Flow manager/flow computer
Hide thumbs Also See for FLOBOSS S600:
Table of Contents

Advertisement

FloBoss S600 Instruction Manual
4.
Place the front of the case against the rear of the prepared cutout.
5.
Re-install the top and bottom bosses, and tighten with a 5.5 mm (5 BA) hex wrench.
6.
When the rear support is fitted, you should use a self-tapping screw to secure the case to the
rear support. The maximum depth of the screw inside the case should be 3 mm (0.12 in.).
2.4.4 Re-installing the Front Panel
The final stage of the installation process is to re-install the front panel on the FloBoss S600 as follows:
1.
Connect the ribbon cable (from the front of the case) to the connector on the front panel.
Observe the orientation of the connector with its mating keyway. The ribbon cable must be
correctly inserted. Do not use excessive force to refit the cable.
2.
Place the top of the front panel over the retaining groove on the top boss and slide downwards.
3.
To secure the front panel, place the hex cap screw into its recess in the bottom center of the
front panel.
Use a 2.5 mm Allen wrench to tighten the screw finger-tight. Turn an additional 180 degrees to
4.
complete the installation.
Take care not to over-tighten the screw. Over-tightening may cause damage to the panel face.

2.5 Installation and Removal of the Boards

The FloBoss S600 unit will be shipped with the boards already installed. If you need to remove the boards
for maintenance or upgrade reasons, please follow the procedures in this section.
The CPU board is dedicated to the left-most rear slot of the case. The remaining slots can be populated
with plug-in I/O boards, or they can be left blank and covered with the blank plates designed for the
purpose.
Ensure suitable electrostatic discharge precautions are taken prior to removing any of the
plug-in boards.
The terminals on some boards may be wired to electrical potentials sufficiently high to cause
electrical shock and injury. Make sure the power sources of any connected devices are
turned off and discharged before performing any installation or repairs.
To remove the plug-in boards:
Ensure the FloBoss S600 is powered-down before attempting to extract a plug-in board.
1.
Unscrew the retention screws before attempting to remove a board to avoid damage to the pull
2.
tabs. Refer to Figure 2-8.
Rev Sep/04