Do NOT proceed if the message FLASH FAILED displays. Remove the power connector
NOTE:
for 5 seconds and re-apply power. The FloBoss S600 will return to the startup menu.
6.
The FloBoss S600 proceeds to erase and reprogram the Flash memory, and displays the following
message:
RESETTING - PLEASE WAIT
The FloBoss S600 then restarts; if the FloBoss S600 has not restarted after 30 seconds, remove the
power connector for 5 seconds to return to the startup menu.
8.3.2 Send and Reflash Config File
To reflash the configuration data:
From the Config 600 software, select the Transfer Data option.
1.
Choose the Comm port connected to the FloBoss S600. Default parameters for serial ports are
2.
38400 bps, 8 data bits, 1 stop bit, and no parity.
NOTE:
Configurations can also be transferred via Ethernet, as well as by the serial
communications port.
Select the configuration you require, then select the sections you desire to transfer to the FloBoss
3.
S600.
4.
Click on Send Now to download to the FloBoss S600.
Once completed, the FloBoss S600 will restart and the Startup menu displays.
8.3.3 Clear SRAM
The Factory Setup options on the Startup menu include Clear SRAM and Format Flash. These options
should only be used under instruction from factory personnel in the event of a problem.
The Clear SRAM option is used to clear out the FloBoss S600 by overwriting the SRAM area. All
battery-backed configuration data will be lost, including system configuration data, process configuration
data, metering totalizers, and network settings.
Following a Clear SRAM command, the FloBoss S600 will restart and return to the Startup menu. The
FloBoss S600 will not be able to warm start again until a full configuration is sent from a PC running
Config 600 software.
To clear the SRAM:
Select FACTORY SETUP from the FloBoss S600 Startup menu.
1.
Select the CLEAR SRAM command.
2.
3.
Press 1 to confirm. The following message displays:
COMMUNICATIONS LINK FAILURE
4.
If after 30 seconds the display has not changed, reboot the FloBoss S600 (power down, wait five
seconds, and then repower). Once completed, the FloBoss S600 Startup menu displays.
Rev Sep/04
Troubleshooting