FloBoss S600 Instruction Manual
A cold start is used after sending a new configuration to the FloBoss S600 or to recover from extreme
situations, such as a corrupted database. A cold start builds a new metering database, using the
configuration data stored in the Flash memory of the FloBoss S600. A cold start must also be performed if
the firmware has been updated or changed.
7.3.1 How to Initiate a Cold Start
You can initiate a Cold Start of the FloBoss S600 using one of two methods.
7.3.1.1 No Power Applied
If the FloBoss S600 is NOT powered up, you may set Bit Link LK13 on the P152 CPU board to the closed
(cold start) position and then apply power to the unit. This will cause the Startup menu to appear.
Exercise CAUTION. When setting the cold start jumper, keep in mind that this setting
NOTE:
will also be used when the FloBoss S600 self starts for any reason, such as a low-voltage shutdown
or recovery from a malfunction. Ensure the cold start jumper setting is removed when not required;
otherwise, an unplanned restart could result in lost data.
Select the COLD START command from the Startup menu. The Startup menu is shown in
1.
Figure 7-1.
2.
Press 1 or 2 to keep or reset the totals.
Press 1 to confirm and the following message displays:
3.
CONFIGURING - PLEASE WAIT
A new database is then built using the configuration files held in the Flash memory.
Once completed, the FloBoss S600 Main menu displays.
7.3.1.2 Power Applied and FloBoss S600 Operating
On a running FloBoss S600, you must set the run mode to Cold Start.
The sequence of keys to access the SYSTEM STATUS page may vary on the displays
NOTE:
for your application.
From the Main menu, select the SYSTEM SETTINGS menu.
1.
Select the SYSTEM STATUS sub-menu.
2.
Press the Chng button.
3.
4.
When the prompt Enter Code: displays, key in your Security Code.
5.
Press 1 to select Cold Start, and press 1 again to confirm.
6.
The FloBoss S600 unit should now perform a reset. If the display has not changed after 30
seconds, power down the FloBoss S600, wait a minimum of five seconds, and then re-apply
power.
7.
This will cause the Startup menu to appear. Follow the steps in Section 7.3.1.1.
A new database is then built using the configuration files held in the Flash memory.
Rev Sep/04
Startup
7-2