4.2.2 Digital Outputs
There are 12 digital output channels. The digital outputs (DIGOUT) are high current, open collector type.
The maximum current rating is 100 mAmps at 24 volts dc. Output frequencies up to 0.5 Hz are possible.
The DC polarity must be carefully checked. Use an external DC supply in series with the load. When
using inductive loads, such as relay coils, place a diode across the load.
The DIGOUT channels CH1 to CH2 are located on connector SKT-E, and channels CH3 and CH12 are
located on connector SKT-F. The DIGOUT pin connections are shown Table 4-17 and Table 4-18. Field
wiring schematics are shown in Figure 4-10 and Figure 4-11 in Section 4.1.4.
Rev Sep/04
Table 4-16. DIGIN Pin Connections for SKT-F
Pin
19
DIGIN-CH7
18
DIGIN-CH8
17
RETURN CH5-8
16
DIGIN-CH9
15
DIGIN-CH10
14
DIGIN-CH11
13
DIGIN-CH12
12
RETURN CH9-12
11
DIGIN-CH13
10
DIGIN-CH14
9
DIGIN-CH15
8
DIGIN-CH16
7
RETURN CH13-16
Table 4-17. DIGOUT Pin Connections for SKT-E
Pin
36
DIGOUT-CH1
37
DIGOUT-CH2
I/O
Function
Function
4-20