Emerson FLOBOSS S600 Instruction Manual page 26

Flow manager/flow computer
Hide thumbs Also See for FLOBOSS S600:
Table of Contents

Advertisement

FloBoss S600 Instruction Manual
3.3.2 EIA-422 (RS-422)/EIA-485 (RS-485) Multi-drop Port
Three EIA-422 (RS-422) or EIA-485 (RS-485) ports are located on the backplate of the P152 CPU board
and provide high speed/long distance links of up to 38400 bps and 1200 m (4000 ft). The ports use the
connector labeled TB-2, which is COM5, COM6, and COM7. The COM5, COM6, and COM7 pin
connections are shown in Table 3-6.
NOTE:
For two-wire EIA-485 (RS-485) installations, jumper TX+ to RX+ and TX- to RX- on the
TB-2 connector on the P152 CPU board .
3.3.3 Ethernet LAN Port
The standard Ethernet port on the backplate of the CPU card is for high-speed communications using an
Ethernet Local Area Network (LAN) architecture. The speed of data transfer is 10M bps when using
10BaseT twisted pair cable.
The port uses a FCC-68 RJ-45 connector. The port is labeled Network on the backplate of the P152 CPU.
It is the standard Ethernet port. No hardware configuration or wiring is required for this communications
port.
NOTE: For information on the optional, second Ethernet port, refer to Section 3.6.
3.3.4 Local Operator PC or Remote Display Port
The connector labeled COM1-2 on the backplate of the P152 CPU board is used to connect the FloBoss
S600 to a remote display (COM1) or the host PC (COM2). The COM1-2 port should not be modified by
the user for other functions.
The COM1-2 port uses a standard 15-way D-type female connector. The COM1-2 pin connections are
shown in Table 3-7.
Rev Sep/04
Table 3-6. COM5, COM6, and COM7 Pin Connections
Channel
COM5
COM6
COM7
Signal
Common
Pin
Function
1
RX-
2
RX+
3
TX-
4
TX+
5
RX-
6
RX+
7
TX-
8
TX+
9
RX-
10
RX+
11
TX-
12
TX+
13
GND
CPU
3-6