Specifications; Protection Elements - GE F60 Instruction Manual

Ur series. feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
2.4SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
NOTE
power system devices via communications or different output contacts. If not specified, the operate times given
here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
RESTRICTED GROUND FAULT
Pickup:
0.005 to 30.000 pu in steps of 0.001
Dropout:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0 x CT rating:
±0.5% of reading or ±1% of rated (which-
ever is greater)
>2.0 x CT rating
±1.5% of reading
Slope:
0 to 100% in steps of 1%
Pickup delay:
0 to 600.00 s in steps of 0.01
Dropout delay:
0 to 600.00 s in steps of 0.01
Operate time:
<1 power system cycle
PHASE/NEUTRAL/GROUND TOC
Current:
Phasor or RMS
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97% to 98% of pickup
Level accuracy:
0.1 to 2.0 × CT:
±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0 × CT:
±1.5% of reading > 2.0 × CT rating
Curve shapes:
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier:
Time Dial = 0.00 to 600.00 in steps of
0.01
Reset type:
Instantaneous/Timed (per IEEE)
Curve timing accuracy
at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
Voltage restraint:
modifies pickup current for voltage in the
range of 0.1<V<0.9 VT Nominal in a
fixed linear relationship
GE Multilin
PHASE/NEUTRAL/GROUND IOC
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
> 2.0 × CT rating
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timer accuracy:
NEGATIVE SEQUENCE TOC
Pickup level:
Dropout level:
Level accuracy:
2
t; FlexCurves™
Curve shapes:
Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01
Reset type:
Curve timing accuracy
at 1.03 to 20 x pickup:
NEGATIVE SEQUENCE IOC
Pickup level:
Dropout level:
Level accuracy:
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timer accuracy:
F60 Feeder Protection System

2.4 SPECIFICATIONS

2.4.1 PROTECTION ELEMENTS

0.000 to 30.000 pu in steps of 0.001
97 to 98% of pickup
(whichever is greater)
±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<16 ms at 3 × pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3 × pickup at 60 Hz
(Neutral IOC)
±3% of operate time or ±1/4 cycle
(whichever is greater)
0.000 to 30.000 pu in steps of 0.001
97% to 98% of pickup
±0.5% of reading or ±0.4% of rated
(whichever is greater)
from 0.1 to 2.0 x CT rating
±1.5% of reading > 2.0 x CT rating
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
2
Extremely Inverse; I
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
Instantaneous/Timed (per IEEE) and Lin-
ear
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
0.000 to 30.000 pu in steps of 0.001
97 to 98% of pickup
0.1 to 2.0 × CT rating: ±0.5% of reading
or ±0.4% of rated (whichever is greater);
> 2.0 × CT rating: ±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<20 ms at 3 × pickup at 60 Hz
±3% of operate time or ±1/4 cycle
(whichever is greater)
2
2-19