Polycom DOC2560C Getting Started Manual page 48

Polycom conference platform getting started guide
Table of Contents

Advertisement

Chapter 2-First Time Installation and Configuration
2-16
4
Using the two wires of an 10 AWG cable running from the DC power
distribution unit, connect the black wire into the -48VDC terminal
block and the red wire to the RTN terminal block.
A 10 AWG cable must be used to connect the mains with the RMX 4000 DC
Power Rail Model.
The supply wires for DC version must be terminated using quick connectors.
Extension cords may not be used.
ESD connector
Ground connector
Circuit breaker - ON
position
RTN
The center PRM slot/module is fitted with a blank panel and the slot cannot be
used on a system with DC Voltage.
5
Connect the green or green-yellow wire to the system single-point
M6x15 "Ground" bolt.
The rating of the protective earthing conductor should be a minimum of 10AWG.
If the unit is rack mounted, the single-point ground on the MCU must
be connected to the rack with a single conductor and fixed as to
prevent loosening. When using bare conductors, they must be coated
Blank panel
-48 VDC
Circuit breaker - OFF
position

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rmx 1500Realpresence rmx 4000Rmx 2000

Table of Contents