2. M-NET control
2-3. System configuration restrictions
2-3-1. Common restrictions for the CITYMULTI system
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
*OA processing unit GUF-RD(H) is considered as Indoor unit.
B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.)
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.
2-3-2. Ensuring proper communication power for M-NET
In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY, and OA processing unit
GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases,
Transmission booster should be used. Taking the power consumption of Indoor unit sized P20-P140 as 1, the equivalent
power consumption or supply of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption
Indoor, OA unit
Indoor unit
BC controller
Sized P15-P140
Sized P200,P250
GUF-50, 100
1
7
*RC : Remote Controller
Table 2-3-2 The equivalent power supply
Transmission Booster
Power supply unit
PAC-SF46EPA
PAC-SC51KUA
25
5
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32. Not
applicable to the PUMY model.
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the
air-conditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, OA process units and ME remote controller, Timers
and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sized
P200, 250 is counted as 7 Indoor units, but MA remote controller(s), LOSSNAY, PZ-60DR-E is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumption
reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA is used to supply power at TB7 side, count from
TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reaches
6, a PAC-SF46EPA should be set.
System example
TB7
TB3
TB7
TB3
Outdoor unit
CENTRALIZED CONTROLLER AG-150A
M-NET
Centralized controller
(AG-150A)
24VDC
Power supply unit
PAC-SC51KUA
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 5.
MA RC. LOSSNAY ME Remote Contr.
PAR-30MAA
PAR-F27MEA
CMB
PAR-21MAA
PAC-SE51CRA
PAC-YT51CRA(B)
PZ-52SF-E
PAR-FA32MA
LGH-RX-E
PZ-60DR-E
2
0
Expansion controller
BM ADAPTER
PAC-YG50ECA
BAC-HD150
6
01
ME remote
controller
Transmission booster (No.1) should be used,
if the total quantity of Indoor units, OA process units and ME remote controllers
reaches 40, (Indoor unit sized P200, 250 is counted as 7);
or if the total equivalent transmission power consumption reaches 32.
LOSSNAY
unit
PZ-52SF-E
N3
SYSTEM DESIGN
Timers, System Contr.
PAC-SC30GRA
AT-50A
PAC-SF44SRA
PAC-YT34STA
AG-150A
1/4
1/2
4
System Controller
GB-50ADA
Connector TB3 and TB7 total *
6
6
TRANSMISSION BOOSTER
POWER RATING
MODEL
PAC-SF46EPA
220-240V:0.7A ~/N
WEIGHT
50
3.4kg
MADE IN JAPAN
Transmission
02
booster
(No.1)
N1
UP
TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA
POWER RATING
WEIGHT
220-240V:0.7A ~/N
50
3.4kg
MADE IN JAPAN
Transmission
booster
LOSSNAY
PAC-SF46EPA
unit
(No.2)
PZ-52SF-E
N4
Within N4, the total equivalent transmission
power consumption should not exceed 25.
ON/OFF Contr.
MN Converter
PAC-YT40ANRA CMS
-MNF-B
1
1/2
Outdoor unit
Outdoor unit
Connector TB7 only
32
UP
ME remote
controller
N2
Within N2, conditions 1,2 should be followed.
1.The total quantity of Indoor units, OA process units
and ME remote controller should not exceed 40.
*Indoor unit sized P200, 250 is counted as 7 units.
2.The total equivalent transmission power consumption
should not exceed 25.
CMS
-MNG-E
2
6
206