2-2.Transmission Cable Specifications - Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book

Table of Contents

Advertisement

2. M-NET control
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
Connected with simple remote controller.
Check the existing wires for damage to insulation by measuring the resistance between the lead and the ground with a 500V
ohmmeter. If the insulation resistance is less than 100 MΩ, replace the wires.
Disconnect all controllers before measuring insulation resistance to avoid controller damage.
Note: Disconnect the system controller before starting a refrigerant oil recovery operation, if one is connected.
Reconnect the system controller after the completion of the refrigerant oil recovery operation.
(L
)
Transmission cables
i
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25
[AWG16]
When 10m [32ft] is exceeded, use cables with
the same specification as transmission cables.
SYSTEM DESIGN
ME Remote controller cables
Sheathed 2-core cable (unshielded)
CVV
2
0.3 1.25
[AWG22 16]
2
(0.75 1.25
[AWG18 16])
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS :
PE insulated PVC jacketed shielded communication cable
CVV
: PV insulated PVC sheathed control cable
MA Remote controller cables
2
0.3 1.25
[AWG22 16]
2
(0.75 1.25
[AWG18 16])
Max length : 200m [656ft]