7. Cooling [Wall mounted]
PKFY-P-VBM-E,VHM-E,VKM-E
Model
Outdoor
size
air temp.
21.5°C D.B.
(Rated kW)
15°C W.B.
°C D.B.
CA
20.0
10.6
22.5
10.6
25.0
10.6
27.5
10.6
30.0
10.4
100
(11.2)
32.5
10.2
35.0
10.0
37.5
9.8
40.0
9.6
43.0
9.4
23°C D.B.
25°C D.B.
16°C W.B.
18°C W.B.
SHC
CA
SHC
CA
7.6
11.0
7.9
11.8
7.6
11.0
7.9
11.8
7.6
11.0
7.9
11.8
7.6
10.9
7.8
11.6
7.5
10.7
7.7
11.3
7.4
10.5
7.6
11.1
7.3
10.3
7.5
10.9
7.2
10.1
7.4
10.7
7.1
9.9
7.3
10.5
7.0
9.7
7.2
10.2
INDOOR UNITS
Indoor air temp.
27°C D.B.
28°C D.B.
19°C W.B.
20°C W.B.
SHC
CA
SHC
CA
7.8
12.1
8.2
12.5
7.8
12.1
8.2
12.5
7.8
12.1
8.2
12.4
7.7
11.9
8.1
12.2
7.6
11.6
8.0
12.0
7.5
11.4
7.9
11.7
7.4
11.2
7.8
11.5
7.3
11.0
7.7
11.3
7.2
10.8
7.6
11.1
7.1
10.5
7.5
10.8
CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
30°C D.B.
32°C D.B.
22°C W.B.
24°C W.B.
SHC
CA
SHC
CA
8.2
13.2
8.1
14.2
8.2
13.2
8.1
14.2
8.1
13.1
8.0
13.9
8.0
12.9
7.9
13.7
7.9
12.6
7.8
13.4
7.9
12.4
7.7
13.1
7.8
12.1
7.6
12.8
7.7
11.9
7.5
12.6
7.6
11.6
7.4
12.3
7.5
11.3
7.3
12.0
kcal/h=kW x 860 , BTU/h = kW x 3,412
SHC
8.0
8.0
7.9
7.8
7.7
7.6
7.5
7.4
7.3
7.2
150