4. Outdoor Installation
In case of collective installation and continuous installation
: Front
A
C
:
Must be open
B
• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and
passageways between groups of units as shown in the figures.
• At least two sides must be left open.
• As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
an asterisk.
• If there is a wall at both the front and the rear of the unit, install up to six units consecutively in the side direction and
provide a space of 1000mm or more as inlet space/passage space for each six units.
B
B
A
C
450*
[17-23/32]
A
[17-23/32]
: Wall height (H)
C
B
A
C
30
[1-3/16]
C
B
A
C
100
[3-15/16]
B
A
A
C
450
450
100*
[17-23/32] [17-23/32] [3-15/16]
B
C
A
A
(Unit : mm [in.])
450
450
[17-23/32]
SYSTEM DESIGN
C
B
A
C
C
A
1000*
B
[39-3/8]
B
B
278